74 Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Chapter 5 Programmable Parameters
NONVOL BAUD RATE
This parameter allows the installer to
manually set the desired baud rate.
Parameter 55, AutoBaud Enable, must be
disabled when using this parameter.
Parameter Number 56
Access Rule Get/Set
Data Type USINT
Object Mapping 0xB4-1-6
Group DeviceNet Setup
Units
Minimum Value 0 = 125k
1 = 250k
Maximum Value 2 = 500k
Default Value 0
COS MASK
This parameter allows the installer to define
the change-of-state conditions that will
result in a change-of-state message being
produced.
1 = Enabled
0 = Disabled
Parameter Number 58
Access Rule Get/Set
Data Type WORD
Object Mapping 0xB4-1-13
Group DeviceNet Setup
Units
Minimum Value 0000000000000000
Maximum Value 0000001111111111
Default Value 0000000000000000
Bit Function:
1514131211109876543210
XTrip
X Warning
X Output A
X Output B (E3 Plus)
X Input #1
X Input #2
X Input #3 (E3 Plus)
X Input #4 (E3 Plus)
X Motor Current
X Ground Fault Current (E3 Plus)
OUTPUT ASSEMBLY
This parameter is used to select the desired
output assembly. See Appendix B for a listing
of available assemblies
Parameter Number 59
Access Rule Get/Set
Data Type USINT
Object Mapping 0xB4-1-16
Group DeviceNet Setup
Units
Minimum Value 0
Maximum Value 105
Default Value 103 (E3)
105 (E3 Plus)