Rockwell-automation 193-EC4 EC4 Current Monitoring Relay User Manual Manual de usuario Pagina 81

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 157
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 80
Rockwell Automation Publication 193-UM011A-EN-P - September 2010 82
Chapter
6
Current Monitoring Parameters
Introduction
This chapter provides information for the current monitoring parameters of the
EC4 Current Monitoring Relay.
Phase Current Reporting
Current Range
The EC4 Current Monitoring Relay utilizes a true RMS algorithm to calculate
the RMS value of the current passing through phase L1, L2, and L3. The relay is
capable of sensing and reporting currents ranging from 0% to 720% of the
maximum current rating.
The following chart illustrates the reporting current precision, the minimum and
maximum reporting current values, and the 720% maximum current rating value
for each current range.
IMPORTANT
The EC4 Current Monitoring Relay will report 0 A if the current is
below 30% of the minimum current rating.
IMPORTANT
The EC4 Current Monitoring Relay is capable of reporting values
greater than 720% of the maximum current rating, but the accuracy of
the value may be compromised.
Vista de pagina 80
1 2 ... 76 77 78 79 80 81 82 83 84 85 86 ... 156 157

Comentarios a estos manuales

Sin comentarios