Rockwell Automation Publication 193-UM011A-EN-P - September 2010 75
Programmable Parameters Chapter 5
INPUT ASSEMBLY
This parameter is used to select the desired
input assembly. See Appendix B for a listing
of available assemblies
Parameter Number 60
Access Rule Get/Set
Data Type USINT
Object Mapping 0xB4-1-17
Group DeviceNet Setup
Units
Minimum Value 0
Maximum Value 107
Default Value 100
ASSY WORD0 PARAM
This parameter assigns the parameter value
to be placed in Word 0 of Input Assembly
100.
Parameter Number 61
Access Rule Get/Set
Data Type USINT
Object Mapping 0xB4-1-7
Group DeviceNet Setup
Units
Minimum Value 0
Maximum Value 89
Default Value 21
ASSY WORD1 PARAM
This parameter assigns the parameter value
to be placed in Word 1 of Input Assembly
100.
Parameter Number 62
Access Rule Get/Set
Data Type USINT
Object Mapping 0xB4-1-8
Group DeviceNet Setup
Units
Minimum Value 0
Maximum Value 89
Default Value 1
ASSY WORD2 PARAM
This parameter assigns the parameter value
to be placed in Word 2 of Input Assembly
100.
Parameter Number 63
Access Rule Get/Set
Data Type USINT
Object Mapping 0xB4-1-9
Group DeviceNet Setup
Units
Minimum Value 0
Maximum Value 89
Default Value 2
ASSY WORD3 PARAM
This parameter assigns the parameter value
to be placed in Word 3 of Input Assembly
100.
Parameter Number 64
Access Rule Get/Set
Data Type USINT
Object Mapping 0xB4-1-10
Group DeviceNet Setup
Units
Minimum Value 0
Maximum Value 89
Default Value 3