Rockwell Automation Publication 193-UM011A-EN-P - September 2010 67
Programmable Parameters Chapter 5
➊
For Catalog Number 193-EC4ZZ
➊ For Catalog Number 193-EC4ZZ
➊ For Catalog Number 193-EC4ZZ
L1 UC Trip Level
This parameter sets the under current trip
level for line 1.
Parameter Number 108
Access Rule Get/Set
Data Type UINT
Object Mapping 2C
hex
-1-159
2C
hex
-1-184 ➊
Group Advanced Setup
Units 0.01 Amps
1 Amps ➊
Minimum Value 0.20
Maximum Value 5000
Default Value
L1 UC Trip Delay
This parameter allows the installer to
program a time duration for which an under
current condition must exist at the
programmed level prior to the device
tripping.
Parameter Number 109
Access Rule Get/Set
Data Type USINT
Object Mapping 2C
hex
-1-160
Group Advanced Setup
Units 0.1 Seconds
Minimum Value 0.1
Maximum Value 25.0
Default Value 1.0
L1 UC Warn Level
This parameter sets the under current
warning level for line 1.
Parameter Number 110
Access Rule Get/Set
Data Type UINT
Object Mapping 2C
hex
-1-161
2C
hex
-1-118 ➊
Group Advanced Setup
Units 0.01 Amps
1 Amps ➊
Minimum Value 0.20
Maximum Value 5000
Default Value
L2 UC Trip Level
This parameter sets the under current trip
level for line 2.
Parameter Number 111
Access Rule Get/Set
Data Type UINT
Object Mapping 2C
hex
-1-162
2C
hex
-1-185 ➊
Group Advanced Setup
Units 0.01 Amps
1 Amps ➊
Minimum Value 0.20
Maximum Value 5000
Default Value