80 Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Chapter 5 Programmable Parameters
DeviceLogix Group
COMM OVERRIDE
This parameter is used to enable DeviceLogix
programs to override normal output behavior
in the event of a communication status
change. These events include all states
where the E3 Plus is without an I/O
connection (I/O Connection does not exist,
has timed out, has been deleted, or is
currently idle)
Parameter Number 79
Access Rule Get/Set
Data Type BOOL
Object Mapping 0x1E-1-105
Group DeviceLogix
Units
Minimum Value 0 = Disabled
Maximum Value 1 = Enabled
Default Value 0
NETWORK OVERRIDE
This parameter is used to enable DeviceLogix
programs to override normal output behavior
in the event of a network fault. Network
faults include duplicate MAC ID failures and
bus off conditions.
Parameter Number 80
Access Rule Get/Set
Data Type BOOL
Object Mapping 0x1E-1-104
Group DeviceLogix
Units
Minimum Value 0 = Disabled
Maximum Value 1 = Enabled
Default Value 0
NET OUTPUTS
This parameter monitors network outputs
controlled through DeviceLogix programs.
Parameter Number 81
Access Rule Get/Set
Data Type WORD
Object Mapping 0x04-1-3
Group DeviceLogix
Units
Minimum Value
Maximum Value
Default Value
Bits Function:
1514131211109876543210
X Net Output 0
X Net Output 1
X Net Output 2
X Net Output 3
X Net Output 4
X Net Output 5
X Net Output 6
X Net Output 7
X Net Output 8
X Net Output 9
X Net Output 10
X Net Output 11
X Net Output 12
X Net Output 13
X Net Output 14
X—