Rockwell-automation 193-EC4 EC4 Current Monitoring Relay User Manual Manual de usuario Pagina 64

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 157
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 63
Rockwell Automation Publication 193-UM011A-EN-P - September 2010 65
Programmable Parameters Chapter 5
IN3 ASSIGNMENT
This parameter allows the user to assign a
specific function to the discrete IN3 input.
Parameter Number 85
Access Rule Get/Set
Data Type USINT
Object Mapping 29
hex
-1-179
Group Advanced Setup
Units
Minimum Value 0 = Normal
1 = Trip Reset
2 = Remote Trip
3 = L1 Loss Arm
4 = L2 Loss Arm
5 = L3 Loss Arm
6 = L1 L2 Loss Arm
7 = L2 L3 Loss Arm
8 = L1 L3 Loss Arm
Maximum Value 9 = L1 L2 L3 Loss Arm
Default Value 0
IN4 ASSIGNMENT
This parameter allows the user to assign a
specific function to the discrete IN4 input.
Parameter Number 86
Access Rule Get/Set
Data Type USINT
Object Mapping 29
hex
-1-180
Group Advanced Setup
Units --
Minimum Value 0 = Normal
1 = Trip Reset
2 = Remote Trip
3 = L1 Loss Arm
4 = L2 Loss Arm
5 = L3 Loss Arm
6 = L1 L2 Loss Arm
7 = L2 L3 Loss Arm
8 = L1 L3 Loss Arm
Maximum Value 9 = L1 L2 L3 Loss Arm
Default Value 0
GF TRIP INHIBIT
This parameter allows the installer to inhibit
a ground fault trip from occurring when the
ground fault current exceeds the maximum
range of the core balance sensor
(approximately 10 A).
Parameter Number 89
Access Rule Get/Set
Data Type BOOL
Object Mapping
Group Advanced Setup
Units --
Minimum Value 0 = Disabled
Maximum Value 1 = Enabled
Default Value 0
Vista de pagina 63
1 2 ... 59 60 61 62 63 64 65 66 67 68 69 ... 156 157

Comentarios a estos manuales

Sin comentarios