Parameter Descriptions
9-49
Displays the status of the control terminal block control inputs.
Important: Actual control commands may come from a source
other than the control terminal block.
Displays the status of the control terminal block digital inputs.
d013 Contrl In Status
Range: 0 = Input Present
1 = Input Not Present
See figure 9.17
Default: Read Only
See also: d002, P034, P035
Figure 9.17 – Contrl In Status (d013) Bit Definitions
1 = Input Present, 0 = Input Not Present
Start / Run FWD Input (I/O Terminal 02) Bit 0
Direction / Run REV Input (I/O Terminal 03) Bit 1
Stop Input
1
(I/O Terminal 01) Bit 2
1
The stop input must be present in order to start the drive.
When this bit is a 1, the drive can be started.
When this bit is a 0, the drive will stop.
Dynamic Brake Transistor On Bit 3
d014 Dig In Status
Range: 0 = Input Not Present
1 = Input Present
See figure 9.18.
Default: Read Only
See also: A051-A054
Figure 9.18 – Dig In Status (d014) Bit Definitions
Digital In1 Sel (I/O Terminal 05) Bit 0
Digital In2 Sel (I/O Terminal 06) Bit 1
Digital In3 Sel (I/O Terminal 07) Bit 2
Digital In4 Sel (I/O Terminal 08) Bit 3