A-2
MD65 AC Drive User Manual
Accel/Decel: Two independently programmable accel and decel
times. Each time may be programmed from 0-600
seconds in 0.1 second increments.
Intermittent
Overload:
• 150% Overload capability for up to 1 minute.
• 200% Overload capacity for up to 3 seconds
Electronic Motor
Overload Protection:
Class 10 protection with speed-sensitive response.
Input/Output Rating
Output Frequency: 0-400 Hz (Programmable)
Efficiency: 97.5% (Typical)
Digital Control Inputs (Inputs Current = 6 mA)
SRC (Source)
Mode:
18-24 V = ON
0-6 V = OFF
SNK (Sink) Mode: 0-6 V = ON
18-24 V = OFF
Analog Control Inputs
4-20 mA Analog: 250 ohm input impedance
0-10 V DC Analog: 100k ohm input impedance
External Pot: 1-10 k ohm, 2 Watt minimum
Control Output
Programmable Output (form C relay)
Resistive Rating: 3.0 A at 30 V DC, 3.0 A at 125 V AC, 3.0 A at
240 V AC
Inductive Rating: 0.5 A at 30 V DC, 0.5 A at 125 V AC, 0.5 A
Opto Outputs
Resistive Rating: 30 V DC, 50 mA
Inductive Rating: Recover diode. Refer to figure 6.1 for details.
Analog Outputs (10-bit)
Rating: 0-10 V, 1k ohm min.
4-20 mA, 525 ohm max
Fuses and Circuit Breakers
Recommended
Fuse Type:
UL Class J, CC, T or Type BS88; 600 V (550 V) or
equivalent.
Recommended
Circuit Breakers:
HMCP circuit breakers or equivalent.