
9-18
MD65 AC Drive User Manual
Scales the Maximum Output Value for the Analog Out Sel (A065)
source setting.
For example:
Sets the rate of acceleration for speed increases except jog. Refer
to the flowchart in figure 6.3 for details. Refer to figure 9.3.
Maximum Frequency / Accel Time = Accel Rate
Sets the rate of deceleration for speed decreases except jog. Refer
to the flowchart in figure 6.3 for details. See figure 9.4.
A066 Analog Out High
Range: 0 to 800%
Default: 100%
See also: A065
A066 Setting A065 Setting A065 Max. Output Value
50% 1 = OutCurr 0-10 5 V for 200% Drive Rated Output Current
90% 8 = OutPowr 0-20 18 mA for 200% Drive Rated Power
A067 Accel Time 2
Range: 0.0 to 600.0 sec
Default: 10.0 sec
See also: P039, A051-A054, A070-A077, A140-A147
Figure 9.3 – Accel Time 2 (A067)
Speed
0
Time
P035 [Maximum Freq]
P039 or A067
[Accel Time x]
P040 or A068
[Decel Time x]
0
Acceleration
D
eceleration
A068 Decel Time 2
Range: 0.1 to 600.0 sec
Default: 10.0 sec
See also: P040, A051-A054, A070-A077, A140-A147
Comentarios a estos manuales