Parameter Descriptions
9-25
Sets the frequency where the break frequency is applied when
Boost Select (A084) is set to 0 = Custom V/Hz, and Torque Perf
Mode (A125) is set to 0 = V/Hz.
Sets the highest voltage the drive will output.
Maximum output current allowed before current limiting occurs.
The drive provides Class 10 motor overload protection. Settings 0-2
select the derating factor for the I
2
t overload function. See figure
9.9.
A087 Break Frequency
Range: 0.0 to 400.0 Hz
Default: 15.0 Hz
See also: P031, P032, P034, P035, A084, A085, A086, A088,
A125
A088 Maximum Voltage
Range: 20 to Drive Rated Volts
Default: Drive Rated Volts
See also: d004, A085, A086, A087
A089 Current Limit 1
Range: 0.1 to (Drive Rated Amps x 1.8)
Default: Drive Rated Amps x 1.8
See also: P033, A118
A090 Motor OL Select
Range: 0 = No Derate
1 = Min Derate
2 = Max Derate
Default: 0 = No Derate
See also: P032
Figure 9.9 – Motor OL Select (A090)
Min D
r
t
1
4
2
N
D
r
t
1
4
2
of P033
Motor OL Curent
M
x D
r
t
1
4
2
2
17
1
12
1
7
2
2
17
1
12
1
7
2
2
17
1
12
1
7
2