MD65 AC Drive User Manual
15 = PID Disable: Disables PID function. Drive uses the next valid
non-PID speed reference.
16 = MOP Up: Increases the value of Internal Freq (A069) at a rate
of 2 Hz per second. Default for A069 is 60 Hz.
17 = MOP Down: Decreases the value of Internal Freq (A069) at a
rate of 2 Hz per second. Default for A069 is 60 Hz.
18 = Timer Start: Clears and starts the timer function. May be used
to control the relay or opto outputs.
19 = Counter In: Starts the counter function. May be used to
control the relay or opto outputs.
20 = Reset Timer: Clears the active timer.
21 = Reset Countr: Clears the active counter.
22 = Rset Tm&Cnt: Clears the active time and counter.
23 = Logic In1: Logic function input number 1. May be used to
control the relay or opto outputs (see parameters A055, A058,
A061, options 11-14). May be used with StepLogic
TM
parameters
A140-A147.
24 = Logic In2: Logic function input number 2. May be used to
control the relay or opto outputs (see parameters A055, A058,
A061, options 11-14). May be used with StepLogic
TM
parameters
A140-A147.
25 = Current Lmt2: When active, Current Limit 2 (A118)
determines the drive current limit level.
26 = Anlg Invert: Inverts the scaling of the analog input levels set in
Anlg In 0-10V Lo (A110), Anlg In 0-10V Hi (A111), Anlg In 4-20mA
Lo (A112), and Anlg In 4-20mA Hi (A113).