Parameter Descriptions
9-35
A setting of 0 disables this parameter.
Sets the time that the drive will remain in stall mode before a fault is
issued.
Figure 9.12 – Skip Freq Band (A120)
Frequency
Time
Skip Frequency
Command
Frequency
Drive Output
Frequency
2x Skip
Frequency Band
A121 Stall Fault Time
Range: 0 = 60 sec
1 = 120 sec
2 = 240 sec
3 = 360 sec
4 = 480 sec
5 = Flt Disabled
Default: 0 = 60 sec
See also: A089-A118
A122 Analog In Loss
Range: 0 = Disabled
1 = Fault (F29)
2 = Stop
3 = Zero Ref
4 = Min Freq Ref
5 = Max Freq Ref
6 = Int Freq Ref
Default: 0 = Disabled
See also: A110, A111, A132