Parameter Descriptions
9-29
Scales the value displayed by Process Display (d010).
Output Frequency x Process Factor = Process Display
Resets a fault and clears the fault buffer (parameters d007 through
d009). Used primarily to clear a fault over network communications.
1 = Reset Fault: Clears the active fault and resets the drive.
2 = Clear Buffer: Clears fault codes from parameters d007 through
d009.
When set to 1 = Locked, protects parameters against change by
unauthorized personnel.
Used by Rockwell Automation field service personnel.
A099 Process Factor (Display Scaling)
Range: 0.1 to 999.9
Default: 30.0
See also: d010
A100 Fault Clear
Range: 0 = Ready/Idle
1 = Reset Fault
2 = Clear Buffer (d007 - d009)
Default: 0 = Ready/Idle
See also: d007 - d009
A101 Program Lock
Range: 0 = Unlocked
1 = Locked
Default: 0 = Unlocked
See also: N/A
A102 Testpoint Sel
Range: 0 to FFFF
Default: 400
See also: d019