Troubleshooting the Drive
10-9
10.2.4 Problem: Motor Does Not Start
Cause(s) Indication Corrective Action
No output voltage to the
motor.
None Check the power circuit.
Check the supply voltage.
Check all the fuses and
disconnects.
Check the motor.
Verify that the motor is
connected properly.
Check the control input
signals
Verify that a Start signal is
present. If 2-Wire control
is used, verify that either
the Run Forward or Run
Reverse signal is active,
but not both.
Verify that I/O Terminal 01
is active.
Verify that Start Source
(P036) matches your
configuration.
Verify that Reverse
Disable (A095) is not
prohibiting movement.
Drive is faulted. Flashing red
STATUS LED.
Clear fault.
Press Stop
Cycle power
Set Fault Clear (A100) to
1 = Clear Faults.
Cycle digital input if Digital
Inx Sel (A051-A054) is set
to 7 = Clear Fault.