Parameter Descriptions
9-7
Maximum Frequency / Decel Time = Decel Rate
Setting this parameter to 1 resets all parameter values to factory
defaults. After the reset function is complete, this parameter sets
itself back to 0. This selection causes an F48 Params Defaulted
fault.
Sets the voltage class of 600V drives.
Figure 9.2 – Decel Time 1 (P040)
Speed
0
Time
P035 [Maximum Freq]
P039 or A067
[Accel Time x]
P040 or A068
[Decel Time x]
0
Acceleration
D
eceleration
P041 Reset To Defalts
Range: 0 = Ready/Idle
1 = Factory Rset
Default: 0 = Ready/Idle
See also: N/A
P042 Voltage Class
Range: 2 = “Low Voltage” 480V
3 = “High Voltage” 600V
Default: 3 = “High Voltage” 600 V
See also: N/A