H-8
MD65 AC Drive User Manual
Table H.4 – Digit 1 – Defines what logic must be met to jump to a step other than the
very next step.
Table H.5 – Digit 0 – Defines what logic must be met to jump to the very next step.
Setting Description Logic
0 Skip Step (jump immediately) SKIP
1 Step based on the time programmed in the respective [Stp Logic Time x] parameter. TIMED
2 Step if “Logic In1” is active (logically true) TRUE
3 Step if “Logic In2” is active (logically true) TRUE
4 Step if “Logic In1” is not active (logically false) FALSE
5 Step if “Logic In2” is not active (logically false) FALSE
6 Step if either “Logic In1” or “Logic In2” is active (logically true) OR
7 Step if both “Logic In1” and “Logic In2” is active (logically true) AND
8 Step if neither “Logic In1” or “Logic In2” is active (logically true) NOR
9 Step if “Logic In1” is active (logically true) and “Logic In2” is not active (logically false) XOR
A Step if “Logic In2” is active (logically true) and “Logic In1” is not active (logically false) XOR
b Step after [Stp Logic Time x] and “Logic In1” is active (logically true) TIMED AND
C Step after [Stp Logic Time x] and “Logic In2” is active (logically true) TIMED AND
d Step after [Stp Logic Time x] and “Logic In1” is not active (logically false) TIMED OR
E Step after [Stp Logic Time x] and “Logic In2” is not active (logically false) TIMED OR
F Do not step OR no “jump to”, so use Digit 0 logic IGNORE
Setting Description Logic
0 Skip Step (jump immediately) SKIP
1 Step based on the time programmed in the respective [Stp Logic Time x] parameter. TIMED
2 Step if “Logic In1” is active (logically true) TRUE
3 Step if “Logic In2” is active (logically true) TRUE
4 Step if “Logic In1” is not active (logically false) FALSE
5 Step if “Logic In2” is not active (logically false) FALSE
6 Step if either “Logic In1” or “Logic In2” is active (logically true) OR
7 Step if both “Logic In1” and “Logic In2” is active (logically true) AND
8 Step if neither “Logic In1” or “Logic In2” is active (logically true) NOR
9 Step if “Logic In1” is active (logically true) and “Logic In2” is not active (logically false) XOR
A Step if “Logic In2” is active (logically true) and “Logic In1” is not active (logically false) XOR
b Step after [Stp Logic Time x] and “Logic In1” is active (logically true) TIMED AND
C Step after [Stp Logic Time x] and “Logic In2” is active (logically true) TIMED AND
d Step after [Stp Logic Time x] and “Logic In1” is not active (logically false) TIMED OR
E Step after [Stp Logic Time x] and “Logic In2” is not active (logically false) TIMED OR
F Use logic programmed in Digit 1 IGNORE