Publication 1760-UM002B-EN-P - March 2005
4-36 Wiring with Pico GFX-70
Coil Negation (Inverse Contactor Function) ]
The output signal is simply an inversion of the input signal; the relay operates
like a contactor with contacts that have been negated. If the coil is triggered
with the 1 state, the coil switches its make contacts to the 0 state.
Figure 4.22 Signal diagram of inverse contactor function
Rising Edge Evaluation (Cycle Pulse) ,
If the coil is only meant to switch on a rising edge, this function will be
applied. With a change in the coil state from 0 to 1, the coil switches its make
contacts to the 1 state for one cycle.
Figure 4.23 Signal diagram of cycle pulse with rising edge
Falling Edge Evaluation (Cycle Pulse)
If the coil is only meant to switch on a falling edge, this function will be
applied. With a change in the coil state from 1 to 0, the coil switches its make
contacts to the 1 state for one cycle.
on
on
on