2-40 Installation
Expanding Inputs/Outputs
You can add expansion units to all GFX types with an expansion I/O socket
to increase the number of inputs and outputs:
Local Expansion
Local expansion units are fitted directly next to the processor unit with the
expansion I/O socket connection.
Figure 2.48 Connecting local expansion units with Pico GFX-70 processors
Table 2.47 Pico Expansion I/O Modules
Processor Unit I/O Modules Description
1760-LDF
1760-LDFA
1760-LDFC
1760-LDFCA
1760-IA12XOW6I 12 AC inputs, 6 relay outputs
1760-IB12XOB8
12
(1)
DC inputs, 8 transistor outputs
(1) Four of the digital dc inputs can alternately be used as 0 to 10V dc analog inputs. These inputs can be used as
either digital or analog, not both. For example you could use 4 analog inputs plus 8 digital inputs.
1760-IB12XOW6I 12 DC inputs, 6 isolated relay outputs
1760-OW2 2 relay outputs
ATTENTION
The following electrical separation is implemented between
the processor unit of the GFX device and the expansion
unit (separation always in local connection of expansion
unit)
Simple isolation 400V ac (+10%)
Safe isolation 240V ac (+10%)
Units may be destroyed if the value 400V ac +10% is
exceeded, and may cause the malfunction of the entire
system or machine.
IMPORTANT
GFX processor units and expansion units can be fed by
different DC power supplies.
processor unit expansion I/O
1760-RPLCONN