Rockwell-automation 1760-xxxx Pico GFX-70 Controllers User Manual Manual de usuario Pagina 226

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 400
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 225
Publication 1760-UM002B-EN-P - March 2005
4-116 Wiring with Pico GFX-70
Parameter Display and Parameter Set for the LS Function Block
Inputs
The function block inputs >I1, >X1, >X2, >Y1 and >Y2 can have the following
operands:
Constants
Markers MD, MW, MB
Analog inputs IA01 to IA04
IA01: terminal I7
IA02: terminal I8
IA03: terminal I11
IA04: terminal I12
Analog output QA01
Actual value
QV> of another function block
Output
The function block output QV> can be assigned the following operands:
Markers MD, MW, MB
Analog output QA01
LS27 +
>I1
>X1
>Y1
>X2
>Y2
QV>
LS27 LS value scaling function block number 27
+ Appears in the parameter display
>I1 Input value, actual value source range
>X1 Lower value of source range
>Y1 Lower value of target range
>X2 Upper value of source range
>Y2 Upper value of target range
QV> Output value, scaled
Vista de pagina 225