Wiring with Pico GFX-70 4-119
Parameter display and parameter set for the LS01 function block:
The actual value at the analog input IA01 is 511.
The scaled output value is 2045.
Example 2:
The source range has 12 bits.
The target range has 16 signed bits.
>I1 = DC01QV
>X1 = 0
>X2 = 4095
>Y1 = -32768
>Y2 = +32767
The actual value at the analog input DC01QV 1789.
The scaled output value is -4137.
Jumps
Jumps can be used to optimize the structure of a circuit diagram or to
implement the function of a selector switch. For example, jumps can be used
to implement whether manual/automatic mode, or different machine
programs are to be selected.
Jumps consist of a jump location and a jump destination (label).
LS01 +
>I1 IA01
>X1 0
>Y1 0
>X2 1023
>Y2 4095
QV>