Rockwell-automation 1760-xxxx Pico GFX-70 Controllers User Manual Manual de usuario Pagina 192

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 400
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 191
Publication 1760-UM002B-EN-P - March 2005
4-82 Wiring with Pico GFX-70
Coils
CH01EN to CH04EN: enable of the counter
CH01D to CH04D: count direction definition,
Status 0 = count upwards,
Status 1 = count downwards
CH01RE to CH04RE: reset actual value to zero
CH01SE to CH04SE: accept preset actual value with rising edge.
Memory Requirement of the High-Speed Counter
The high-speed counter function block requires 52 bytes of memory plus 4
bytes per constant on the function block inputs.
Retention
High-speed counter relays can be operated with retentive actual values. The
number of retentive counter relays can be selected in the SYSTEM
RETENTION menu.
If a counter relay is retentive, the actual value is retained when the operating
mode changes from RUN to STOP as well as when the power supply is
switched off.
If Pico GFX-70 is started in RUN mode, the counter relay operates with the
retentively saved actual value.
Vista de pagina 191
1 2 ... 187 188 189 190 191 192 193 194 195 196 197 ... 399 400

Comentarios a estos manuales

Sin comentarios