Rockwell-automation 1760-xxxx Pico GFX-70 Controllers User Manual Manual de usuario Pagina 254

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 400
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 253
Publication 1760-UM002B-EN-P - March 2005
4-144 Wiring with Pico GFX-70
Figure 4.66 Signal diagram of timing relay, on-delayed
(with and without random switching)
1: trigger coil T..EN
2: stop coil T..ST
3: reset coil T..RE
4: switching contact (make contact) T..Q1
t
s
: setpoint time
Range A:
The set time elapses normally.
Range B:
The entered setpoint does not elapse normally because the trigger coil drops out prematurely.
Range C:
The Stop coil stops the time from elapsing.
t
1
+ t
2
= t
s
t
A
B
t
s
1
2
4
3
C
Vista de pagina 253
1 2 ... 249 250 251 252 253 254 255 256 257 258 259 ... 399 400

Comentarios a estos manuales

Sin comentarios