9-4 Troubleshooting
Diagnostic items are provided for each respective channel.
The following diagnostic items can be accessed using DriveExplorer
v3.01 (or higher).
Viewing Module Diagnostic Items
Table 9.A Diagnostic Items for Module in Single Mode
No. Name Description
1Reserved —
2 Logic Cmd Current value of the product-specific Logic Command being
transmitted to the drive by this module.
3 Reference Current value of the product-specific Reference being
transmitted to the drive by this module.
4Reserved —
5 Logic Sts Current value of the product-specific Logic Status being
received from the drive by this module.
6 Feedback Current value of the product-specific Feedback being
received from the drive by this module.
7-22 Reserved —
23 DSI Overrun Errs Number of DSI receive overrun errors.
24 DSI Framing Errs Number of DSI receive framing errors.
25 DSI CRC Errs Number of DSI receive CRC errors.
26 Boot Flash Count Number of times the boot firmware in the module has been
flash updated.
27 App Flash Count Number of times the application firmware in the module has
been flash updated.
Table 9.B Diagnostic Items for Module in Multi-Drive Mode
No. Name Description
1Reserved —
2 Drv 0 Logic Cmd Current value of the product-specific Logic Command being
transmitted to Drive 0 by this module.
3 Drv 0 Reference Current value of the product-specific Reference being
transmitted to Drive 0 by this module.
4Reserved —
5 Drv 0 Logic Sts Current value of the product-specific Logic Status being
received from Drive 0 by this module.
6 Drv 0 Feedback Current value of the product-specific Feedback being
received from Drive 0 by this module.
7 Drv 1 Logic Cmd Current value of the product-specific Logic Command being
transmitted to Drive 1 by this module.
8 Drv 1 Reference Current value of the product-specific Reference being
transmitted to Drive 1 by this module.
Comentarios a estos manuales