Rockwell-automation 1769-SM2 Compact I/O DSI/Modbus Communication Modu Manual de usuario Pagina 65

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 204
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 64
Chapter 5
Understanding Explicit Messaging
This chapter provides information about explicit messaging.
Explicit messaging is used to read/write data that is not part of the
module’s I/O Image (Chapter
4), such as:
Reading/writing drive parameters.
Operating as a Modbus RTU Master and initiating Request/Response
messages to Modbus RTU Slave devices, such as PowerFlex 7-Class
drives with 20-COMM-H adapters.
The following table shows various products that can be used with the
1769-SM2 module and whether they support explicit messaging:
Contact your local Rockwell Automation, Inc. representative for
inquiries about the explicit message capabilities of products not
specified above.
Topic Page
Formatting Explicit Messages
5-2
Modbus RTU Master Operation Messages 5-9
Products
Supports Explicit Messaging
Yes No
MicroLogix 1500 LRP Series A and B, and
LSP processors
MicroLogix 1500 LRP Series C (or newer) and
RSLogix 500 v6.30 (or higher)
Important: This LRP processor supports messaging
only for the first two I/O modules capable of messaging.
RSLogix 500 versions prior to v6.30
Enhanced CompactLogix processors such as the -L31,
-L32E, and -L35E
CompactLogix -L20 and -L30 processors
1769-ADN DeviceNet adapter (see documentation for
possible future explicit messaging support)
!
ATTENTION: Hazard of equipment damage exists. If Explicit
Messages are programmed to write parameter data to Non-Volatile
Storage (NVS) frequently, the NVS will quickly exceed its life cycle
and cause the drive to malfunction. Do not create a program that
frequently uses Explicit Messages to write parameter data to NVS.
Vista de pagina 64
1 2 ... 60 61 62 63 64 65 66 67 68 69 70 ... 203 204

Comentarios a estos manuales

Sin comentarios