2-8 Installing the Module
Figure 2.5 1769-SM2 Module with Remote 1769-Based Adapter
Panel Mounting Procedure Using Module as a Template
The following procedure enables you to use the assembled modules as a
template for drilling holes in the panel. Due to module mounting hole
tolerance, it is important to follow these steps:
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the
center of all module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including
any previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8
screw (not included).
5. Place the modules back on the panel, and check for proper hole
alignment.
6. Attach the modules to the panel using the mounting screws.
DIN Rail Mounting
The 1769-SM2 module can be mounted using these DIN rails:
35 x 7.5 mm (EN 50 022 - 35 x 7.5)
35 x 15 mm (EN 50 022 - 35 x 15)
When mounting the module to a DIN rail, make sure that the latches are
closed and properly securing the module.
D
P
I / S
C
A
N
port
MODULE
CH1
CH2
CH3
C
H
1
C
H
2
C
H
3
132 mm (5.19 in)
122.6 mm (4.83 in)
118 mm (4.65 in)
147.4 mm (5.81 in)
14.7 mm
(0.58 in)
35 mm
(1.38 in)
35 mm
(1.38 in)
28.5 mm
(1.12 in)
35 mm
(1.38 in)
70 mm
(2.76 in)
35 mm
(1.38 in)
35 mm
(1.38 in)
35 mm
(1.38 in)
50 mm
(1.97 in)
40 mm
(1.58 in)
59 mm
(2.32 in)
59 mm
(2.32 in)
Mounting Hole
Dimension
DIN Rail
Center Line
MS
IO
NS
DIAG