3-4 Configuring the Module
The configuration data directly correlates to the module parameters.
Refer to Appendix B for more information.
Entering MicroLogix 1500 Configuration Data Using RSLogix 500
Before v6.30
Earlier versions of RSLogix 500 can be used, but the configuration data
must be entered in raw form in a Data Config table following the format
in Table 3.C
. However, RSLogix 500 v6.30 (or higher) is highly
recommended for use with the 1769-SM2 because it contains a dedicated
I/O configuration window for the module to simplify the configuration
process. Version 6.30 is also required to perform explicit messaging,
such as parameter reads/writes.
Entering MicroLogix 1500 Configuration Data Using RSLogix 500
v6.30 (or higher)
Allocate and enter the configuration data by performing these steps:
1. In the RSLogix 500 treeview, double-click on I/O Configuration to
open the I/O Configuration window. Double-click the 1769-SM2 in
the Current Cards Available list to add the module to the controller
system. Select the “1769-SM2” row and click the A
dv Config
command button. The 1769-SM2 I/O Configuration window
(Figure 3.1
) appears.
Figure 3.1 I/O Configuration Window and Expansion General Configuration Screen