Rockwell-automation 6000 PowerFlex Medium Voltage Variable Frequency D Manual de usuario Pagina 29

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 98
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 28
Rockwell Automation Publication 6000-IN006A-EN-P - April 2014 29
Drive Mechanical Installation Chapter 2
Figure 18 - Aligning Cabinets with Drawout Power Modules (6/6.6 kV shown)
Isolation Transformer Cabinet
Power Module/LV Control Cabinet
Bypass Cabinet
(Optional)
Table 6 - Sidesheet Openings
Front Wireway
Rear Wireway
U Phase Motor Cable
V Phase Motor Cable
W Phase Motor Cable
Ground Bus Connection
Voltage Sensing
Board Cables
Isolation Transformer Secondary
Cables
(1)
(2)
(1) The number of Isolation Transformer secondary
cables is dependent on motor voltage class.
• 9 cables per motor phase (27 total) for 3/3.3 kV
•18 cables per motor phase (54 total) of 6/6.6 kV
• 27 cables per motor phase (81 total) for 10 kV
(2) 6/6.6 kV configurations only require 18 cable
hole locations per phase. Extra cable hole
locations allow for added installation flexibility.
❹❺
Front
Front
❽❽
❼❼
SIDE VIEW
Vista de pagina 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 97 98

Comentarios a estos manuales

Sin comentarios