88 Rockwell Automation Publication 6000-IN006A-EN-P - April 2014
Appendix F Power Cabling and Control Signal Wiring Details
Figure 53 - Typical Terminal Strip Wiring Diagram Drive System with a Bypass Cabinet
KM1NO
KM2NO
KM3NO
KM1NC
KM2NC
KM3NC
QS1NO
QS2NO
QS1NC
QS2NC
From
Customer
From CB
Spare
To DCS
L 220V AC
N 0V AC
MV Closed
L 220V AC
N 0V AC
MV Pre-closed CB
MV Closed
MV Opening
Warning
Drive Running
Drive Stop
Ready
Control
Fault
MV Pre-closed CB
MV Closed
Warning
Drive Running
Drive Stop
Ready
DCS
Control
Fault
Pre-closed CB
CB Open
Emergency Stop
Bypass Choice
Drive Choice
Output Current
4...20 mA
Output Frequency
4...20 mA
DCS Stop
Spare
Speed Input
4...20 mA
Anlg Input 4...20 mA
spare
Anlg Input 4...20 mA
spare
24V DC
DCS Fault reset
Spare
Spare
DCS Start
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
NOTE:
1. 4...20 mA shielded cable from customer input shall be
grounded at the inverter side.
2. Remote DCS DI input to drive shall be of pulse type with a
duration of 3 seconds.
3. Connection marked with dotted line shall be in the
customer’s scope of supply.
Drive Choice
Bypass Choice
Drive to Bypass
Bypass to Drive
Modbus/RS485
Spare
From Remote DCS
To Remote DCS
From Remote DCS
To Remote DCS
From Remote DCS