Rockwell Automation Publication 6000-IN006A-EN-P - April 2014 35
Drive Mechanical Installation Chapter 2
Table 8 - Power Module Specifications
Figure 24 - Drawout Power Module Lifting Handles
Type Output Rating (Amps) Dimensions (HxWxD), approx. Weight, approx.
Fixed-mounted ≤150 A 420 x 180 x 615 mm (16.5 x 7.1 x 24.2 in.) 20 kg (44.1 lb)
151...200 A 420 x 260 x 615 mm (16.5 x 10.2 x 24.2 in.) 25 kg (55.1 lb)
Drawout 201...380 A 575 x 342 x 691 mm (22.6 x 13.5 x 27.2 in.) 40 kg (88.2 lb)
381...420 A 575 x 342 x 910 mm (22.6 x 13.5 x 35.8 in.) 50 kg (110.2 lb)
ATTENTION: Two people are required to handle the Power Modules. Always
handle the drawout Power Modules using the two recessed lifting handles on
both mounting rails (Figure 24
).
Recessed Lifting Handles
Mounting Rail
ATTENTION: Do not use the front mounted positioning handles for lifting the
Power Modules. They are designed to position or withdraw the Power Module
when on the tray assembly.
Comentarios a estos manuales