54 Rockwell Automation Publication 6000-IN006A-EN-P - April 2014
Chapter 3 Drive Electrical Installation
When the doors of the Power Module/LV Control Cabinet or Isolation
Transformer Cabinet are not closed, when the drive is being maintained or when
the control power switch is not closed, the drive will not send a signal allowing
the input circuit breaker to close; this is wired as a permissive contact in the input
circuit breakers closing circuit so that the input circuit breaker cannot close.
Wire Routing and Connection
The electrical safety interlock control signal wiring enters the drive through the
same opening as the control power wiring in the bottom of the LV Control
Cabinet (Figure 31
or Figure 32).
The wiring terminates to the X1 terminal block strip on the right side of the LV
Control cabinet (Figure 33
). See Figure 50 or Figure 51 for general information.
Refer to Electrical Drawings for actual connection points.