Rockwell Automation Publication 6000-IN006A-EN-P - April 2014 87
Power Cabling and Control Signal Wiring Details Appendix F
Figure 52 - Terminal Strip Wiring Diagram for Drive System without a Bypass Cabinet
L 220V AC
From
Customer
From CB
Spare
To Remote DCS
To CB
From Remote DCS
N 0V AC
MV Closed
L 220V AC
N 0V AC
MV Pre-closed CB
MV Closed
MV Opening
Warning
Drive Running
Drive Stop
Ready
Control
Fault
MV Pre-closed CB
MV Closed
Warning
Drive Running
Drive Stop
Ready
DCS
Control
Fault
Pre-closed CB
CB Open
Emergency Stop
Output Current
4...20 mA
Output Frequency
4...20 mA
DCS Stop
Spare
Speed Input
4...20 mA
Anlg Input 4...20 mA
spare
Anlg Input 4...20 mA
spare
24V DC
DCS Fault reset
Spare
Spare
DCS Start
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Modbus/RS485
NOTE:
1. 4...20 mA shielded cable from customer input shall be
grounded at the inverter side.
2. Remote DCS DI input to drive shall be of pulse type with a
duration of 3 seconds.
3. Connection marked with dotted line shall be in the
customer’s scope of supply.
Spare
From Remote DCS
To Remote DCS
From Remote DCS