Rockwell-automation GMLC Reference Manual Manual de usuario Pagina 740

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 958
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 739
Publication GMLC-5.2 - November 1999
Using Block Transfers 703
Program Listing Report PLC-5/30
Rung 2:0
EXAMPLE OF SENDING DATA TO THE MOTION CONTROLLER
| BLOCK BLOCK |
| TRANSFER S CLASS TRANSFER |
| SEND DATA BTW BTR PROGRAM WRITE |
| CONDITION ENABLE ENABLE RUNNING CONTROL |
| I:002 N10:0 N10:5 I:011 +BTW-----------------+ |
+----] [------]/[-------]/[-------] [------+BLOCK TRNSFR WRITE +-(EN)-+
| 00 15 15 10 |Rack 01| |
| |Group 0+-(DN) |
| |Module 0| |
| |Control Block N10:0+-(ER) |
| |Data file N13:0| |
| |Length 0| |
| |Continuous N| |
| +--------------------+ |
Other interlocks in the BTW rung can be required for your application. At
a minimum, you should have all of the following:
A condition that causes the BTW (don’t send a BTW on every PLC
scan).
The enable bits (Bit 15 of the BT control block) of all other block
transfers in the ladder.
The block transfer length should always be set to zero, as shown in the
ladder above. This causes all 64 words of the data file to be sent. In
addition, continuous block transfers should not be used.
Using the enable bits from each block transfer to interlock all other block
transfers ensures that the block transfers always occur in the order in
which they appear in the PLC ladder. This is the same technique used to
interlock other RIO devices.
Vista de pagina 739
1 2 ... 735 736 737 738 739 740 741 742 743 744 745 ... 957 958

Comentarios a estos manuales

Sin comentarios