
Publication GMLC-5.2 - November 1999
786 1394 GMC Turbo SLC Interface
5. Select OK. The dialog box closes, and the new input appears in the
Tag Window.
Defining Input Floats
If you have enabled input floats (see Defining the I/O Configuration), you
must link each floating point input to a user variable that holds the
floating point value. To do this:
1. In the Tag Explorer, select Input Float.
2. In the Tag Window, single-click the right mouse button. A variable
short-cut menu appears.
3. Select New. The SLC Input Float dialog box appears.
Address Type the address, or number, of the bit (from 0
to 39).
Note: The available address range depends
upon the number of Input Bits you
specified in the SLC page of the
Configure Control Options dialog box.
See
Defining the I/O Configuration
.
Field Description
Comentarios a estos manuales