Publication GMLC-5.2 - November 1999
Using Block Transfers 705
Getting Data from the Motion Controller
A block transfer write (BTW), followed immediately by a block transfer
read (BTR), is used to get (read) data from the motion controller. The
BTW specifies the data to be read; the BTR reads the current values and
stores them in a data file in the PLC. Every BTR must be preceded with a
BTW to set up the values to be read.
For example, the PLC rungs below execute a BTW to request the data
specified in PLC data file N14 from the motion controller, and a BTR to
read the data from the motion controller and store it in PLC data file N7
when a switch (I:002/01) is closed. The specified data is read
continuously while the switch is closed.
Program Listing Report PLC-5/30
Rung 2:0
EXAMPLE OF GETTING DATA FROM THE MOTION CONTROLLER.
| BLOCK BLOCK |
| TRANSFER S CLASS TRANSFER |
| GET DATA BTW BTR PROGRAM WRITE |
| CONDITION ENABLE ENABLE RUNNING CONTROL |
| I:002 N10:0 N10:5 I:011 +BTW-----------------+ |
+----] [------]/[-------]/[-------] [------+BLOCK TRNSFR WRITE +-(EN)-+
| 01 15 15 10 |Rack 01| |
| |Group 0+-(DN) |
| |Module 0| |
| |Control Block N10:0+-(ER) |
| |Data file N14:0| |
| |Length 0| |
| |Continuous N| |
| +--------------------+ |
Rung 2:1
ONCE THE BTW HAS REQUESTED THE DATA, A BTR IS PERFORMED TO READ IT.
| BLOCK |
| TRANSFER S CLASS |
| GET DATA BTW BTR PROGRAM |
| CONDITION ENABLE ENABLE RUNNING |
| I:002 N10:0 N10:5 I:011 +BTR-----------------+ |
+----] [------]/[-------]/[-------] [------+BLOCK TRNSFR READ +-(EN)-+
| 01 15 15 10 |Rack 01| |
| |Group 0+-(DN) |
| |Module 0| |
| |Control Block N10:5+-(ER) |
| |Data file N7:0| |
| |Length 0| |
| |Continuous N| |
| +--------------------+ |