Rockwell-automation 22-COMM-E EtherNet/IP Adapter Manual de usuario Pagina 47

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 166
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 46
Using I/O Messaging 5-3
When enabled, Reference/Feedback begins at word 1 in the I/O image.
The Reference (16 bits) is produced by the controller and consumed by
the adapter. The Feedback (16 bits) is produced by the adapter and
consumed by the controller.
The example ladder logic program works with a ControlLogix controller
and a PowerFlex 40 drive.
Function of the Example Program
This example program enables you to:
Obtain status information from the drive.
Use the Logic Command to control the drive (for example, start, stop).
Send a Reference to the drive and receive Feedback from the drive.
Adapter Setting for the Example Program
Adapter IP address 10. 91. 97. 74 is set using parameters.
The adapter is configured for Single mode (Operating Mode Switch is
set to “Single”).
RSLogix 5000 Configuration
Controller Tags
When you add the adapter and drive to the I/O configuration (see
Chapter 4
), RSLogix 5000 automatically creates controller tags for them.
In this example program, the following controller tags are used.
Using Reference/Feedback
Size Valid Values
(1)
(1)
The Reference for a PowerFlex 4 or 40 is set in Hz. and not in engineering
units like other PowerFlex drives. For example, “300” equates to 30.0 Hz
(the decimal point is always implied).
In I/O Image Example
16-bit 0.0 to 240.0 Hz (PowerFlex 4) or
0.0 to 400.0 Hz (PowerFlex 40)
Word 1 Figure 5.1
Example Ladder Logic Program
Vista de pagina 46
1 2 ... 42 43 44 45 46 47 48 49 50 51 52 ... 165 166

Comentarios a estos manuales

Sin comentarios