Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 123
Using Explicit Messaging Chapter 6
ControlLogix Controller Example Ladder Logic Program to Write a Single
Parameter, RSLogix 5000 Software, All Versions
A Set Attribute Single message is used to write to a single parameter. This write
message example writes a value to parameter 140 - [Accel Time 1] in a PowerFlex
7-Class drive.
Table 23 - Example Controller Tags to Write a Single Parameter
Figure 51 - Example Ladder Logic to Write a Single Parameter
ControlLogix Controller – Formatting a Message to Write a Single Parameter,
RSLogix 5000 Software, All Versions
Figure 52 - Set Attribute Single Message Configuration Screens
Operand Controller Tags for Single Write Message Data Type
XIC Execute_Single_Write_Message BOOL
MSG Single_Write_Message MESSAGE