Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 147
Troubleshooting Chapter 7
Using the HIM to View Adapter Diagnostic Items
Table 24 - Adapter Diagnostic Items
Step Example Screen
1. Access parameters in the adapter. See Using the PowerFlex 7-
Class HIM on page 28.
2. Press the or key to scroll to Diagnostics.
3. Press the (Enter) key to display the Diagnostics menu in the
adapter.
4. Repeat steps 2 and 3 to enter the Device Items option.
5. Press the or key to scroll through the items.
Main Menu:
Diagnostics
Parameter
Device Select
Device Item # 3
Reference
No. Name Description
1 Common Logic Cmd The present value of the Common Logic Command being transmitted to the drive by this adapter.
2 Prod Logic Cmd The present value of the Product Logic Command being transmitted to the drive by this adapter from the controller.
3 Reference
The present value of the Reference being transmitted to the drive by this adapter. Note that a 16-bit value will be
sent as the Most Significant Word of the 32-bit field.
4 Common Logic Sts The present value of the Common Logic Status being received from the drive by this adapter.
5 Prod Logic Sts The present value of the Product Logic Status being received from the drive by this adapter to the controller.
6 Feedback
The present value of the Feedback being received from the drive by this adapter. Note that a 16-bit value will be
sent as the Most Significant Word of the 32-bit field.
7 Datalink A1 In
The present value of respective Datalink In being transmitted to the drive by this adapter. (If not using a Datalink,
this parameter should have a value of zero.)
8 Datalink A2 In
9 Datalink B1 In
10 Datalink B2 In
11 Datalink C1 In
12 Datalink C2 In
13 Datalink D1 In
14 Datalink D2 In
15 Datalink A1 Out
The present value of respective Datalink Out being received from the drive by this adapter. (If the drive indicates a
16-bit datalink size, the value appears in the least significant 16 bits of this diagnostic item, and the most significant
16 bits of this diagnostic item are zero.)
16 Datalink A2 Out
17 Datalink B1 Out
18 Datalink B2 Out
19 Datalink C1 Out
20 Datalink C2 Out
21 Datalink D1 Out
22 Datalink D2 Out
23 DPI Rx Errors The present value of the DPI Receive error counter.
24 DPI Rx Error Max The maximum value (since reset) of the DPI Receive error counter.
25 DPI Tx Errors The present value of the DPI Transmit error counter.
26 DPI Tx Error Max The maximum value (since reset) of the DPI Transmit error counter.
27 Boot Flash Count Number of times the boot firmware in the adapter has been flash updated.
28 App Flash Count Number of times the application firmware in the adapter has been flash updated.
29 M-S Input Size Size of data transferred from the network to the drive.
30 M-S Output Size Size of data transferred from the drive to the network.