Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 69
Configuring the I/O Chapter 4
Figure 12 - Example MicroLogix 1100/1400 Controller EtherNet/IP Network
Configuring Parameters for Network I/O
Because the I/O for the drive is message-based, there is no need to configure any
I/O inside the RSLogix 500 project, version 7.00 or later, until using the I/O as
described in Chapter 5
.
However, to get the adapter to operate with the I/O created in Chapter 5
, we
need to configure the adapter to accept the I/O and drive to point to the
appropriate Datalinks.
1. For this example, the following adapter I/O parameters are set to the
following values.
2. Reset the adapter (see Resetting the Adapter
on page 43) or power cycle
the drive.
For the drive speed reference and Datalink parameter values and the
adapter setup parameter values, refer to Drive and Adapter Parameter
Settings on page 96.
IP Address 10.91.100.81
MicroLogix 1100/1400 Controller
IP Address 10.91.100.79
PowerFlex 70 Drive with
20-COMM-ER Adapter
Computer with
Ethernet Connection
Ethernet
Switch
TIP
Information for PowerFlex 750-Series drives has been added where applicable.
Adapter Parameter No. Setting
25 - [DPI I/O Cfg] xxxx xxxx xxx1 1111
37 - [M-S Input] xxxx xxxx xxx1 1111
38 - [M-S Output] xxxx xxxx xxx1 1111