Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 175
Adapter Parameters Appendix B
26 [DPI I/O Act]
Displays the I/O that the adapter is actively
transmitting. The value of this parameter will
usually be equal to the value of Parameter 25 -
[DPI I/O Cfg].
Default: xxx0 0001
Bit Values: 0 = I/O Disabled
1 = I/O Enabled
Type: Read Only
27 [Flt Cfg Logic]
Sets the Logic Command data that is sent to the
drive if any of the following is true:
· Parameter 23 - [Comm Flt Action] is set to ‘4’
(Send Flt Cfg) and I/O communication is
disrupted.
· Parameter 24 - [Idle Flt Action] is set to ‘4’
(Send Flt Cfg) and the controller is idle.
· Parameter 43 - [Peer Flt Action] is set to ‘4’
(Send Flt Cfg) and peer I/O communication is
disrupted.
The bit definitions will depend on the product to
which the adapter is connected. See Appendix
D
or the documentation for the drive being used.
Default: 0000 0000 0000 0000
Minimum: 0000 0000 0000 0000
Maximum: 1111 1111 1111 1111
Type: Read/Write
Reset Required: No
28 [Flt Cfg Ref]
Sets the Reference data that is sent to the drive if
any of the following is true:
· Parameter 23 - [Comm Flt Action] is set to ‘4’
(Send Flt Cfg) and I/O communication is
disrupted.
· Parameter 24 - [Idle Flt Action] is set to ‘4’
(Send Flt Cfg) and the controller is idle.
· Parameter 43- [Peer Flt Action] is set to ‘4’
(Send Flt Cfg) and peer I/O communication is
disrupted.
Default: 0
Minimum: 0
Maximum: 4294967295
Type: Read/Write
Reset Required: No
Important: If the drive uses a 16-bit
Reference, the most significant word of
this value must be set to zero (0) or a
fault will occur.
Parameter
No. Name and Description Details
Bit
Definition
Not Used
Not Used
Not Used
Datalink D
Datalink C
Datalink B
Datalink A
Cmd/Ref
Default xxx00001
Bit 76543210