Rockwell-automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Commun Manual de usuario Pagina 183

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 238
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 182
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 183
EtherNet/IP Objects Appendix C
Class Attributes
Instance Attributes
Assembly Object
Class Code
Services
Instances
Class Attributes
Attribute ID Access Rule Name Data Type Description
2 Get Max Instance WORD Total number of instances
Attribute ID Access Rule Name Data Type Description
1 Get Vendor ID WORD 1 = Allen-Bradley
2GetDevice TypeWORD 123
3 Get Product Code WORD Number identifying product name and rating
4GetRevision:
Major
Minor
STRUCT of:
BYTE
BYTE
Value varies
Value varies
5 Get Status WORD Bit 0 = Owned
Bit 8 = Minor recoverable fault
Bit 10 = Major recoverable fault
6 Get Serial Number DWORD Unique 32-bit number
7 Get Product Name SHORT_STRING Product name and rating
8 Get State USINT Always returns 3 (Operational)
9 Get Configuration
Consistency Value
UINT For the Host (Instance #1) the CCV is determined from the Host's
NVS Checksum along with 20-COMM-ER's NVS Checksum.
For DPI Peripherals (Instances 2-15) the CCV is from the
peripheral's NVS Checksum only.
Hexadecimal Decimal
0x04 4
Implemented for:
Service Code Class Instance Service Name
0x0E Yes Yes Get_Attribute_Single
0x10 Yes Yes Set_Attribute_Single
Instance Description
1 All I/O data being read from the DPI device (read-only)
2 All I/O data written to the DPI device (read/write)
191 Input only
192 Listen only
Attribute ID Access Rule Name Data Type Description
1 Get Revision WORD 2
2 Get Max Instance WORD 2
100 Set Control Timeout WORD Control timeout in seconds
Vista de pagina 182
1 2 ... 178 179 180 181 182 183 184 185 186 187 188 ... 237 238

Comentarios a estos manuales

Sin comentarios