Rockwell-automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Commun Manual de usuario Pagina 137

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 238
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 136
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 137
Using Explicit Messaging Chapter 6
The following table identifies the data that is required in each box to configure a
message to read multiple parameters.
MicroLogix 1100/1400 Controller Example Scattered Read Request Data
In this message example, we use the data table addresses in Figure 71 or Figure 71
to store the request values to be read from these drive parameters.
See DPI Parameter Object on page 198 (Class code 0x93) for parameter
numbering.
Figure 71 - Example Scattered Read Request Data File for PowerFlex 7-Class Drive
General Tab Example Value Description
Channel
Comm… Command
Data Table Address
Size in Bytes
Extended Routing…
Service
(1)
Service Code
Class
Instance
Attribute
1
CIP Generic
N60:0
30
(2)
RIX19:0
Custom
4B (Hex.)
93 or 9F (Hex.)
(3)
0 (Dec.)
0 (Dec.)
Controller port to which the network is connected.
Used to access the Parameter Object in the adapter.
An unused controller data table address containing the message
instruction. This address is the starting word of the destination file.
Number of bytes to be transferred. Each byte size is an 8-bit integer.
An unused routing information file for the controller.
Required for scattered messages.
Code for the requested service.
Class ID for the DPI Parameter Object.
Required for scattered messages.
Required for scattered messages.
MultiHop Tab Example Value Description
To Address 10.91.100.79 IP address of the adapter connected to the drive.
(1) The default setting for Service is ‘Custom’, enabling entry of a Service Code not available from the Service pull-down menu. When
choosing a Service other than ‘Custom’ from the pull-down menu, an appropriate Hex. value is automatically assigned to the
Service Code box which is dimmed (unavailable).
(2) In this example, we are reading five parameters. Each parameter being read requires three contiguous 16-bit words. Scattered
read messages always assume that every parameter being read is a 32-bit parameter, regardless of its actual size. Therefore, the
Size in Bytes must be set to 30. The data structure format is the same as shown on page 141
. Maximum length is 66 words (132
bytes), which equates to 22 parameters. For parameter numbering, see DPI Parameter Object
on page 198 (Class code 0x93).
(3) See Table 17 on page 106
for limitations of PowerFlex 7-Class drives when using DPI Parameter Object Class code 0x93 for explicit
messaging.
PowerFlex 7-Class Drive
Parameter 001 - [Output Freq]
Parameter 003 - [Output Current]
Parameter 006 - [Output Voltage]
Parameter 012 - [DC Bus Voltage]
Parameter 017 - [Analog In1 Value]
Vista de pagina 136
1 2 ... 132 133 134 135 136 137 138 139 140 141 142 ... 237 238

Comentarios a estos manuales

Sin comentarios