
Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013 107
Using Multi-Drive Mode Chapter 7
Multi-Drive Mode Explicit
Messaging
Parameter addressing for Explicit messaging is different in Multi-drive mode than
in Single-drive mode. In Single-drive mode, the Instance value in the message
equals the desired parameter number in the drive. In Multi-drive mode, an
Instance table is used to account for the parameters in the adapter and up to 5
drives. The parameters in the adapter and each of the drives are offset by 400 hex
(1024 decimal):
For example, to access [Accel Time 1] (parameter P041 in PowerFlex 525 and
P109 in PowerFlex 4M) in each of the drives, the following Instances would be
used:
• Drive 0 (PowerFlex 525) Instance = 41(0 + 41)
• Drive 1 (PowerFlex 4M) Instance = 17517 (17408 + 109)
• Drive 2 (PowerFlex 4M) Instance = 18541 (18432 + 109)
• Drive 3 (PowerFlex 4M) Instance = 19565 (19456 + 109)
• Drive 4 (PowerFlex 4M) Instance = 20589 (20480 + 109)
Drive 1 Explicit Message Example
The Explicit message examples in the CompactLogix example program perform a
read and a write to PowerFlex 4M parameter P109 [Accel Time 1]. The
configuration for the read is shown in Parameter Read Message Configuration
on
page 108 and the write is shown in Parameter Write Message Configuration on
page 108.
Instance (Hex.) Instance (Dec.) Device Parameter
0x0000...0x3FFF 0...16383 Drive 0 0...1023
0x4000...0x43FF 16384...17407 Interface
(1)
(1) Interface is the current interface being used to access the information. Note: If using the embedded EtherNet/IP adapter, this
instance range contains the same data as Drive 0.
0...1023
0x4400...0x47FF 17408...18431 Drive 1 0...1023
0x4800...0x4BFF 18432...19455 Drive 2 0...1023
0x4C00...0x4FFF 19456...20479 Drive 3 0...1023
0x5000...0x53FF 20480...21503 Drive 4 0...1023
0x5400...0x57FF 21504...22527 Option 0...1023
Comentarios a estos manuales