
Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013 117
Appendix A
Specifications
Appendix A presents the specifications for the adapter.
Communication
Regulatory Compliance
See the PowerFlex 525 Adjustable Frequency AC Drive User Manual,
publication 520-UM001
for regulatory compliance information.
Network
Protocol
Data Rates
EtherNet/IP
10 Mbps Full Duplex, 10 Mbps Half Duplex, 100 Mbps Full Duplex or 100 Mbps
Half Duplex
Connection Limit 8 TCP connections
4 simultaneous CIP connections including 1 exclusive-owner I/O connection
The following activities use a CIP connection:
• Class I I/O connections (for example, from a ControlLogix or CompactLogix
controller) or CIP Motion connection
• Explicit messaging where “connected” is chosen (for example, in a check box
in RSLogix 5000/Logix Designer)
The following activities DO NOT use a CIP connection:
• Explicit messaging-based control using PCCC or the Register or Assembly
objects, including the MicroLogix 1100/1400 examples in Chapter 4
• Explicit messaging where “connected” is NOT chosen, which is typically the
default
Requested Packet Interval (RPI) 5 ms minimum
Packet Rate Up to 200 total I/O packets per second (100 in and 100 out)
Comentarios a estos manuales