108 Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013
Chapter 7 Using Multi-Drive Mode
Parameter Read Message Configuration
Parameter Write Message Configuration
The Class Code is “f ” for the Parameter Object and the Instance Attribute is “1”
to select retrieving the parameter value. See Appendix C
, Parameter Object for
more information. The Instance value is “17517” to access parameter P109
[Accel Time 1] in the first daisy-chained drive.
The Explicit message for Drive 1 to Drive 4 are identical except for the Instance
values, see Multi-Drive Mode Explicit Messaging
on page 107 for examples.
Additional Information
When the PowerFlex 525 drive (Drive 0) is powered up, all configured
daisy-chained drives must be present before an I/O connection is allowed
on EtherNet/IP (before the drives can be controlled).
If the PowerFlex 525 drive (Drive 0) is powered down, communications
with the four daisy-chained drives (Drive 1 to Drive 4) are disrupted and
the drives will take their corresponding Comm Loss Actions.