Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013 119
Appendix B
Adapter Parameters
Appendix B provides information about the parameters used to configure the
embedded EtherNet/IP adapter.
Parameter List
The parameters are displayed in a Numbered List view order.
Topic Page
Parameter List 119
Parameter
No. Name and Description Details
C121 [Comm Write Mode]
Saves parameter values in active drive memory (RAM) or in
drive non-volatile memory (EEPROM).
Important: Parameter values set prior to setting 1 “RAM only
are saved in RAM.
Default: 0 = Save
Values: 0 = Save
1 = RAM only
Typ e: Re ad/Write
Reset Required:
C122 [Cmd Stat Select]
Selects velocity-specific or position/fibers-specific Command
and Status Word bit definitions for use over a communication
network.
This parameter cannot be changed when an I/O connection is
established through the communication adapter or the drives
embedded EtherNet/IP port.
Default: 0 = Velocity
Values: 0 = Velocity
1 = Position
Typ e: Re ad/Write
Reset Required: Yes
C123 [RS485 Data Rate]
Sets the communications baud rate (bits/second) for the RS485
port. A reset or power cycle is required after selection is made.
Default: 3 = 9600
Values: 0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19,200
5 = 38,400
Typ e: Re ad/Write
Reset Required: Yes
C124 [RS485 Node Addr]
Sets the Modbus drive node number (address) for the RS485
port if using a network connection. A reset or power cycle is
required after selection is made.
Default: 100
Minimum: 1
Maximum: 247
Typ e: Re ad/Write
Reset Required: Yes
C125 [Comm Loss Action]
Sets the drive's response to a loss of connection or excessive
communication errors on the RS485 port.
Default: 0 = Fault
Values: 0 = Fault
1 = Coast Stop
2 = Stop
3 = Continu Last
Typ e: Re ad/Write
Reset Required: No
C126 [Comm Loss Time]
Sets the time that the drive remains in communication loss with
the RS485 port before taking the action specified in C125
[Comm Loss Action].
Important: This setting is effective only if I/O that controls the
drive is transmitted through the RS485 port.
Default: 5.0 s
Minimum: 0.1 s
Maximum: 60.0 s
Typ e: Re ad/Write
Reset Required: No