Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013 127
EtherNet/IP Objects Appendix C
Instance Attributes
Attribute ID Access Rule Name Data Type Description
1 Get Vendor ID UINT 1 = Allen-Bradley
2 Get Device Type UINT 150
3 Get Product Code UINT Number identifying product name and rating
4 Get Revision:
Major
Minor
STRUCT of:
USINT
USINT
Value varies
Value varies
5 Get Status UINT Bit 0 = Owned
Bit 8 = Minor recoverable fault
Bit 10 = Major recoverable fault
6 Get Serial Number UDINT Unique 32-bit number
7 Get Product Name SHORT_STRING Product name and rating
9GetConfiguration
Consistency
Value
UNIT Current Parameter NVS CRS value