IntelliVAC™ Plus ContactorControl ModuleBulletin 1503VCUser Manual
viii Table of Contents 1503-UM054C-EN-P – June 2013
Chapter 7 1503-UM054C-EN-P – June 2013 Communications The communications systems implemented within the IntelliVAC Plus product can be divided in
7-2 Communications 1503-UM054C-EN-P – June 2013 the RS485 interface, for both the IntelliVAC Base and IntelliVAC Enhanced modules. This inte
Communications 7-3 1503-UM054C-EN-P – June 2013 If AutoBaud is enabled then the DNet Baud that was selected will be overridden with the
7-4 Communications 1503-UM054C-EN-P – June 2013 DeviceNet Profile The IntelliVAC Plus is defined within the “miscellaneous device” object c
Communications 7-5 1503-UM054C-EN-P – June 2013 Hold State In general when the hold state option is selected the unit will continue to
7-6 Communications 1503-UM054C-EN-P – June 2013 Mask HIM/PC Logic mask 3 is considered a test and diagnostic state. As such if network comm
Chapter 8 1503-UM054C-EN-P – June 2013 Configuration/Programming Configuration IB Board DIP Switches Some of the functionality of
8-2 Configuration/Programming 1503-UM054C-EN-P – June 2013 This set of switches defines the amount of time, after an OPEN
Configuration/Programming 8-3 1503-UM054C-EN-P – June 2013 Contactor Type This set of switches defines the type of vacuum contactor that is
8-4 Configuration/Programming 1503-UM054C-EN-P – June 2013 Time Delay Undervoltage Configuration (TDUV) This setting controls the amount of
Chapter 1 1503-UM054C-EN-P –June 2013 Product Description Introduction This document contains information for the Allen-Bradley Bulletin 150
Configuration/Programming 8-5 1503-UM054C-EN-P – June 2013 This function is useful for applications that require a contactor to re-close aft
8-6 Configuration/Programming 1503-UM054C-EN-P – June 2013 MC RS485 Addressing This set of DIP switches defines the RS485 address of the Int
Configuration/Programming 8-7 1503-UM054C-EN-P – June 2013 Table 8.K – Termination Resistor Installation in IntelliVAC MC System Units in MC
8-8 Configuration/Programming 1503-UM054C-EN-P – June 2013 Programming the IntelliVAC Base Module The IntelliVAC base module firmware is up
Configuration/Programming 8-9 1503-UM054C-EN-P – June 2013 Move the application disable jumper to the “Program” position as noted on th
8-10 Configuration/Programming 1503-UM054C-EN-P – June 2013 Figure 8.5 – IntelliVAC Plus Bootloader Menu Select the option “Upda
Configuration/Programming 8-11 1503-UM054C-EN-P – June 2013 Figure 8.6 – IntelliVAC Base Bootloader Menu The IntelliVAC base bootloade
8-12 Configuration/Programming 1503-UM054C-EN-P – June 2013 Figure 8.7 – IntelliVAC Base Programming Completed Upload New Firmware Th
Configuration/Programming 8-13 1503-UM054C-EN-P – June 2013 Figure 8.8 - Upload new firmware prompt and send file dialog box After sele
8-14 Configuration/Programming 1503-UM054C-EN-P – June 2013 Upon completion of the transfer the transfer dialog box will disappear. The CRC
1-2 Product Description 1503-UM054C-EN-P –June 2013 Description IntelliVAC Plus is an efficient and flexible solution for controlling me
Configuration/Programming 8-15 1503-UM054C-EN-P – June 2013 Updating the IntelliVAC Plus using Control Flash In order to update the firmwar
8-16 Configuration/Programming 1503-UM054C-EN-P – June 2013 Figure 8.12 - Select IntelliVAC Plus in Control Flash • After selecting “OK
Configuration/Programming 8-17 1503-UM054C-EN-P – June 2013 Figure 8.13 Firmware Update Complete I M P O R T A N TI M P O R T A N T It wil
8-18 Configuration/Programming 1503-UM054C-EN-P – June 2013
Chapter 9 1503-UM054C-EN-P – June 2013 DeviceLogix DLX – DeviceLogix refers to the integrated logic capability of the IntelliVAC Plus . IE
9-2 DeviceLogix 1503-UM054C-EN-P – June 2013 Direct Commands Direct commands are specific commands such as 'open contactor 1' or &
DeviceLogix 9-3 1503-UM054C-EN-P – June 2013 DeviceLogix What is DeviceLogix DeviceLogix functionality has been added to
9-4 DeviceLogix 1503-UM054C-EN-P – June 2013 • Device Input – A physical input of the device. Device inputs represent the actual inputs, s
DeviceLogix 9-5 1503-UM054C-EN-P – June 2013 A connection (wire) between function blocks is defined when an input pin of one function
9-6 DeviceLogix 1503-UM054C-EN-P – June 2013 Launching the DeviceLogix Editor After you configure the properties for the IntelliVAC Plus,
Product Description 1-3 1503-UM054C-EN-P – June 2013 Figure 1.3 – IntelliVAC Plus Base Model
DeviceLogix 9-7 1503-UM054C-EN-P – June 2013 Selection Dialog, you are prompted to select the editor type that you want to launch. Selec
9-8 DeviceLogix 1503-UM054C-EN-P – June 2013 Figure 9.2 – Select Logic Editor Type I M P O R T A N TI M P O R T A N T The IntelliVAC P
DeviceLogix 9-9 1503-UM054C-EN-P – June 2013 1. Upload Logic To upload logic click the Upload Logic icon or alternatively select Com
9-10 DeviceLogix 1503-UM054C-EN-P – June 2013 6. Verify Logic To verify the logic’s syntax, click the Verify icon in the standard toolbar
DeviceLogix 9-11 1503-UM054C-EN-P – June 2013 DeviceLogix Function Block Elements Function block elements consist of: • I/O compon
9-12 DeviceLogix 1503-UM054C-EN-P – June 2013 Digital Output Point (DOP) The following kinds of digital outputs are supported: • Physic
DeviceLogix 9-13 1503-UM054C-EN-P – June 2013
9-14 DeviceLogix 1503-UM054C-EN-P – June 2013 Boolean Function Blocks The following truth table describe the boolean function blocks by list
DeviceLogix 9-15 1503-UM054C-EN-P – June 2013 Table 9.C – Bistable Function Block Output Table Function Reset Input (Set) Output Val
9-16 DeviceLogix 1503-UM054C-EN-P – June 2013 timer resets the output to FALSE the pulse timer can again trigger the process by sensing a FALS
1-4 Product Description 1503-UM054C-EN-P –June 2013 Description (cont.) BASE MODULEIntelliVAC MODULE I/OTOP VIEWCUSTOMER I/OMCBASE CONNECTOR
DeviceLogix 9-17 1503-UM054C-EN-P – June 2013 If the timer senses a TRUE level on the RESET input at any time during the operation of
9-18 DeviceLogix 1503-UM054C-EN-P – June 2013 output remains TRUE, and the accumulator is cleared, essentially ignoring the input. If the tim
DeviceLogix 9-19 1503-UM054C-EN-P – June 2013 Figure 9.9 – Timing Diagram for the Counter Function with a Preset Value = 3 Table
9-20 DeviceLogix 1503-UM054C-EN-P – June 2013 Figure 9.10 – Timing Diagram for the Up/Down Counter with a Preset Value = 3 Table
DeviceLogix 9-21 1503-UM054C-EN-P – June 2013 • Clear Latched hardware faults Go Online Once you’ve created your logic and set up you
9-22 DeviceLogix 1503-UM054C-EN-P – June 2013 Figure 9.11 – Modify Function Block Attributes In order to change a value: 1. Double-
DeviceLogix 9-23 1503-UM054C-EN-P – June 2013 1. Select Tools>Edit so that a check mark appears on the menu, indicating that you
9-24 DeviceLogix 1503-UM054C-EN-P – June 2013 Add a digital output point (DOP) In order to add an output tab click the “Bit Output” button.
DeviceLogix 9-25 1503-UM054C-EN-P – June 2013 Note: A double arrow will appear on the connection for which data has been assumed avai
9-26 DeviceLogix 1503-UM054C-EN-P – June 2013 To apply forces, right click on the input or output element you wish to force. A pop-up appea
Product Description 1-5 1503-UM054C-EN-P – June 2013 A wide range of supply voltage (110 – 240 V AC 50/60Hz, 110 - 250 V DC) all
DeviceLogix 9-27 1503-UM054C-EN-P – June 2013 Figure 9.16 – Input Forced Indication Forcing Outputs The following list describes
9-28 DeviceLogix 1503-UM054C-EN-P – June 2013 Figure 9.18 – Dual Function Bit Behavior In Figure 9.18, the “Stop” output tag is connect
DeviceLogix 9-29 1503-UM054C-EN-P – June 2013 Customized Logic Mode: This mode allows the user to freely create control logic using al
9-30 DeviceLogix 1503-UM054C-EN-P – June 2013 IBX-Input2 This bit represents the status of the corresponding “open” input on the IntelliVAC
DeviceLogix 9-31 1503-UM054C-EN-P – June 2013 JOG This is a dual function bit which can be used to represent the status of a “JOG” pus
9-32 DeviceLogix 1503-UM054C-EN-P – June 2013 Test Mode Status This is a dual function bit which can be used to describe the status of a sel
DeviceLogix 9-33 1503-UM054C-EN-P – June 2013 IBX-Mechanical latch Fail to Trip This is a fault bit which only applies to a mechanica
9-34 DeviceLogix 1503-UM054C-EN-P – June 2013 IBX-Under voltage with close command present This is a warning bit which will be set when the
DeviceLogix 9-35 1503-UM054C-EN-P – June 2013 Output bits/tags Hardware Boolean Outputs Net out A This bit controls the status of
9-36 DeviceLogix 1503-UM054C-EN-P – June 2013 Net Out9/Speed SW FWD Status This is the output portion of the Speed SW FWD Status dual functi
1-6 Product Description 1503-UM054C-EN-P –June 2013 circuits to reduce thermal output and decrease sensitivity to leakage current. Refer to
DeviceLogix 9-37 1503-UM054C-EN-P – June 2013 This is the output portion of the “Start” dual function bit. Net Out 28/Stop This is the
9-38 DeviceLogix 1503-UM054C-EN-P – June 2013 This is an example of a basic logical replacement for a typical relay control circuit. Pushin
DeviceLogix 9-39 1503-UM054C-EN-P – June 2013 After selecting the desired control program the IntelliVAC Plus module must be reset to
9-40 DeviceLogix 1503-UM054C-EN-P – June 2013
Chapter 10 1503-UM054C-EN-P – June 2013 Troubleshooting IB Operational Troubleshooting Procedures The following table identifies possible causes
10-2 Troubleshooting 1503-UM054C-EN-P – June 2013 Table 10.A – IB Operational Troubleshooting Procedures (cont.) LED Color State Condition/P
Troubleshooting 10-3 1503-UM054C-EN-P – June 2013 Table 10.A – IB Operational Troubleshooting Procedures (cont.) LED Color State Condi
10-4 Troubleshooting 1503-UM054C-EN-P – June 2013 Table 10.A – IB Operational Troubleshooting Procedures (cont.) LED Color State Condition/P
Troubleshooting 10-5 1503-UM054C-EN-P – June 2013 Table 10.B - IE Operations Troubleshooting Procedures (cont.) Plus Status LED Color
10-6 Troubleshooting 1503-UM054C-EN-P – June 2013 Table 10.B - IE Operations Troubleshooting Procedures (cont.) Plus Status LED Color State
Product Description 1-7 1503-UM054C-EN-P – June 2013 For further information regarding programming of firmware see Chapter 8 “Configurati
Troubleshooting 10-7 1503-UM054C-EN-P – June 2013 Table 10.B - IE Operations Troubleshooting Procedures (cont.) Plus Status LED Color
10-8 Troubleshooting 1503-UM054C-EN-P – June 2013 Table 10.C – IE Operational Trouble Shooting Procedures (cont.) 7-Segment Display State Co
Troubleshooting 10-9 1503-UM054C-EN-P – June 2013 Table 10.C – IE Operational Trouble Shooting Procedures (cont.) 7-Segment Display Sta
10-10 Troubleshooting 1503-UM054C-EN-P – June 2013 Table 10.D – MC Operational Troubleshooting Procedures 7-Segment Display State Condition/
Appendix A 1503-UM054C-EN-P – June 2013 Fuse Protection Introduction The IntelliVAC module requires external fuse protection to coordinate wi
A-2 Fuse Protection 1503-UM054C-EN-P – June 2013
Appendix B 1503-UM054C-EN-P – June 2013 Parameters Introduction This section provides a detailed description of the parameters used in the c
B-2 Parameters 1503-UM054C-EN-P – June 2013 Table B.1 – Status Word for IB1 Bit Enum Text Description 0 Bit 0: unused unused 1 Bit 1: unused
Parameters B-3 1503-UM054C-EN-P – June 2013 Table B.3 – Conversion Table Binary Hex Binary Hex Binary Hex Binary Hex 0000 0 0100 4
B-4 Parameters 1503-UM054C-EN-P – June 2013 Auxiliary Input Status from IntelliVAC Base Unit #2 [IB 2 Module Aux. Status] Parameter Number: 2
1-8 Product Description 1503-UM054C-EN-P –June 2013 Through RSNetWorx, IntelliVAC Plus firmware version can be viewed in device general page
Parameters B-5 1503-UM054C-EN-P – June 2013 Auxiliary Input Status from IntelliVAC Base Unit #4 [IB 4 Module Aux. Status] Parameter Numbe
B-6 Parameters 1503-UM054C-EN-P – June 2013 Close Input Status from IntelliVAC Base Unit #1 [IB 1 Module Close Status] Parameter Number: 6,5,
Parameters B-7 1503-UM054C-EN-P – June 2013 Close Input Status from IntelliVAC Base Unit #3 [IB 3 Module Close Status] Parameter Number:
B-8 Parameters 1503-UM054C-EN-P – June 2013 Close Input Status from IntelliVAC Base Unit #5 [IB 5 Module Close Status] Parameter Number: 10,_
Parameters B-9 1503-UM054C-EN-P – June 2013 Open Input Status from IntelliVAC Base Unit #2 [IB 2 Module Open Status] Parameter Number:
B-10 Parameters 1503-UM054C-EN-P – June 2013 Open Input Status from IntelliVAC Base Unit #4 [IB 4 Module Open Status] Parameter Number: 14,12
Parameters B-11 1503-UM054C-EN-P – June 2013 Close Coil Command for IntelliVAC Base Unit #1 [IB 1 Close Coil Command] Parameter Number:
B-12 Parameters 1503-UM054C-EN-P – June 2013 Close Coil Command for IntelliVAC Base Unit #3 [IB 3 Close Coil Command] Parameter Number: 18,15
Parameters B-13 1503-UM054C-EN-P – June 2013 Close Coil Command for IntelliVAC Base Unit #5 [IB 5 Close Coil Command] Parameter Number:
B-14 Parameters 1503-UM054C-EN-P – June 2013 Trip Coil Command for IntelliVAC Base Unit #2 [IB 2 Trip Coil Command] Parameter Number: 22,18,1
Product Description 1-9 1503-UM054C-EN-P – June 2013 Specifications (cont.) Table 1.B – Electrical Ratings Main Input Voltage (L1 to L2/
Parameters B-15 1503-UM054C-EN-P – June 2013 Trip Coil Command for IntelliVAC Base Unit #4 [IB 4 Trip Coil Command] Parameter Number:
B-16 Parameters 1503-UM054C-EN-P – June 2013 Contactor Relay Status for IntelliVAC Base Unit #1 [IB 1 Contactor Status Relay Status] Parameter
Parameters B-17 1503-UM054C-EN-P – June 2013 Contactor Relay Status for IntelliVAC Base Unit #3 [IB 3 Contactor Status Relay Status] Para
B-18 Parameters 1503-UM054C-EN-P – June 2013 Contactor Relay Status for IntelliVAC Base Unit #5 [IB 5 Contactor Status Relay Status] Parameter
Parameters B-19 1503-UM054C-EN-P – June 2013 Module Status Relay Status for IntelliVAC Base Unit #2 [IB 2 Module Status Relay Status] Par
B-20 Parameters 1503-UM054C-EN-P – June 2013 Module Status Relay Status for IntelliVAC Base Unit #4 [IB 4 Module Status Relay Status] Parameter
Parameters B-21 1503-UM054C-EN-P – June 2013 Close Coil Current for IntelliVAC Base Unit #1 [IB 1 Close Current] Parameter Number: 36,2
B-22 Parameters 1503-UM054C-EN-P – June 2013 Close Coil Current for IntelliVAC Base Unit #3 [IB 3 Close Current] Parameter Number: 38,31,24,_
Parameters B-23 1503-UM054C-EN-P – June 2013 Close Coil Current for IntelliVAC Base Unit #5 [IB 5 Close Current] Parameter Number: 40_,
B-24 Parameters 1503-UM054C-EN-P – June 2013 Hold Coil Current for IntelliVAC Base Unit #2 [IB 2 Hold Current] Parameter Number: 42,34,26,18,
Important User InformationRead this document and the documents listed in the Additional Resources section about installation, configuration, and opera
1-10 Product Description 1503-UM054C-EN-P –June 2013 5.1 (0.20)Dimensions in mm (inches)29.7(1.17)174.8(6.88)185.3(7.29)59.4(2.34)165.9 (6.53)5
Parameters B-25 1503-UM054C-EN-P – June 2013 Hold Coil Current for IntelliVAC Base Unit #4 [IB 4 Hold Current] Parameter Number: 44,36,
B-26 Parameters 1503-UM054C-EN-P – June 2013 Trip Coil Current for IntelliVAC Base Unit #1 [IB 1 Trip Current] Parameter Number: 46,37,28,19,
Parameters B-27 1503-UM054C-EN-P – June 2013 Trip Coil Current for IntelliVAC Base Unit #3 [IB 3 Trip Current] Parameter Number: 48,39,
B-28 Parameters 1503-UM054C-EN-P – June 2013 Trip Coil Current for IntelliVAC Base Unit #5 [IB 5 Trip Current] Parameter Number: 50,_,_,_,_.
Parameters B-29 1503-UM054C-EN-P – June 2013 Input Line Voltage for IntelliVAC Base Unit #2 [IB 2 Line Voltage] Parameter Number: 52,42
B-30 Parameters 1503-UM054C-EN-P – June 2013 Input Line Voltage for IntelliVAC Base Unit #4 [IB 4 Line Voltage] Parameter Number: 54,44,_,_,_
Parameters B-31 1503-UM054C-EN-P – June 2013 DC Bus Voltage for IntelliVAC Base Unit #1 [IB 1 DC Bus Voltage] Parameter Number: 56,45,3
B-32 Parameters 1503-UM054C-EN-P – June 2013 DC Bus Voltage for IntelliVAC Base Unit #3 [IB 3 DC Bus Voltage] Parameter Number: 58,47,36,_,_.
Parameters B-33 1503-UM054C-EN-P – June 2013 DC Bus Voltage for IntelliVAC Base Unit #5 [IB 5 DC Bus Voltage] Parameter Number: 60,_,_,
B-34 Parameters 1503-UM054C-EN-P – June 2013 Enhanced Module Hardware Output State [IE Hardware Outputs] Parameter Number: 62,50,38,26,14. Ac
Product Description 1-11 1503-UM054C-EN-P – June 2013
Parameters B-35 1503-UM054C-EN-P – June 2013 DeviceNet Voltage [24V DeviceNet Voltage] Parameter Number: 64,52,40,28,16. Access rule:
B-36 Parameters 1503-UM054C-EN-P – June 2013 Table B.6 – DeviceLogix Programs Bit Enum Text Description 0 User customized DeviceLogix Prog. Cu
Parameters B-37 1503-UM054C-EN-P – June 2013 IntelliVAC Plus Action on Loss of DeviceNet Communications [Loss Communication Action] Parame
B-38 Parameters 1503-UM054C-EN-P – June 2013 Table B.8 – Consumed Network Bits Bit Enum Text Description 0 Consumed Network Bit 0 Status of C
Parameters B-39 1503-UM054C-EN-P – June 2013 Produced Network Bits [Produced Network Bits] Parameter Number: 71,59,47,35,22. Access rule
B-40 Parameters 1503-UM054C-EN-P – June 2013 Discrete Output Point Fault Action [DOP Fault Action] Parameter Number: 72,60,48,36,23. Access ru
Parameters B-41 1503-UM054C-EN-P – June 2013 Discrete Output Point Idle Value [DOP Idle Value] Parameter Number: 75,63,51,34,26. Access
B-42 Parameters 1503-UM054C-EN-P – June 2013 DeviceNet Media Access Carrier Identification [DNet MAC ID] Parameter Number: 77,65,53,41,28. Ac
Parameters B-43 1503-UM054C-EN-P – June 2013 Enabling of the AutoBaud Rate Feature [Autobaud Enable] Parameter Number: 79,67,55,43,30. A
B-44 Parameters 1503-UM054C-EN-P – June 2013 Status of the Change Of State Mask [Status COS Mask] Parameter Number: 82,70,58,46,33. Access rul
Chapter 2 1503-UM054C-EN-P – June 2013 Receiving and Storage Receiving Upon receiving the controller, remove the packing and check for damag
Parameters B-45 1503-UM054C-EN-P – June 2013 Status of the Change Of State Mask [Set to Defaults] Parameter Number: 83,71,59,47,34. Acce
B-46 Parameters 1503-UM054C-EN-P – June 2013 Selects the Format of the I/O Data Consumed [Consumed IO Assy] Parameter Number: 84,72,60,48,35.
Parameters B-47 1503-UM054C-EN-P – June 2013 Table B.14 – Format of I/O Data Produced Value Enum Text Description 10 Default Produced As
B-48 Parameters 1503-UM054C-EN-P – June 2013 Table B.15 – Network Output COS Mask Definition (cont.) Bit Enum Text Description Action 10 Net
Parameters B-49 1503-UM054C-EN-P – June 2013 Configuration Parameters Altitude Above Sea Level [Altitude] Parameter Number: 87,7
B-50 Parameters 1503-UM054C-EN-P – June 2013 Real Time Clock Time [RTC Time] Parameter Number: 89,77,65,53,40. Access rule: Get/Set Data Ty
Parameters B-51 1503-UM054C-EN-P – June 2013 Table B.17 – RTC World Time Zone Selection Local (cont.) Value Enum Text Description 13 GM
B-52 Parameters 1503-UM054C-EN-P – June 2013 Override the Loss of an IO Connection [Comm Override] Parameter Number: 92,80,68,56,43. Access ru
Parameters B-53 1503-UM054C-EN-P – June 2013 Type of Contactor Selected for IB2 [IB 2 Contactor Type] Parameter Number: 94,82,70,58,_. A
B-54 Parameters 1503-UM054C-EN-P – June 2013 Type of Contactor Selected for IB4 [IB 4 Contactor Type] Parameter Number: 96,84,_,_,_. Access ru
2-2 Receiving and Storage 1503-UM054C-EN-P – June 2013
Parameters B-55 1503-UM054C-EN-P – June 2013 Time Delay UnderVoltage Setting for IB1 [IB 1 TDUV Configure] Parameter Number: 98,85,72,5
B-56 Parameters 1503-UM054C-EN-P – June 2013 Time Delay UnderVoltage Setting for IB3 [IB 3 TDUV Configure] Parameter Number: 100,87,74,_,_. A
Parameters B-57 1503-UM054C-EN-P – June 2013 Time Delay UnderVoltage Setting for IB5 [IB 5 TDUV Configure] Parameter Number: 102,_,_,_,
B-58 Parameters 1503-UM054C-EN-P – June 2013 Power-Up Safety Setting for IB2 [IB 2 Power-Up Safety Setting] Parameter Number: 104,90,76,62,_.
Parameters B-59 1503-UM054C-EN-P – June 2013 Power-Up Safety Setting for IB4 [IB 4 Power-Up Safety Setting] Parameter Number: 106,92,_,
B-60 Parameters 1503-UM054C-EN-P – June 2013 Learn Mode Setting From IB1 [IB 1 Learn Mode Setting] Parameter Number: 108,93,78,63,47. Access
Parameters B-61 1503-UM054C-EN-P – June 2013 Learn Mode Setting From IB3 [IB 3 Learn Mode Setting] Parameter Number: 110,95,80,_,_. Acc
B-62 Parameters 1503-UM054C-EN-P – June 2013 Learn Mode Setting From IB5 [IB 5 Learn Mode Setting] Parameter Number: 112,_,_,_,_. Access rule
Parameters B-63 1503-UM054C-EN-P – June 2013 Drop Out Time Setting for IB2 [IB 2 Drop Out Time] Parameter Number: 114,98,82,66,_. Acces
B-64 Parameters 1503-UM054C-EN-P – June 2013 Drop Out Time Setting for IB4 [IB 4 Drop Out Time] Parameter Number: 116,100,_,_,_. Access rule:
Chapter 3 1503-UM054C-EN-P – June 2013 Installation General Precautions In addition to the precautions listed throughout this manual, th
Parameters B-65 1503-UM054C-EN-P – June 2013 Drop Out Time Setting From IB1 DIP Switches [IB 1 Drop Out Time DIP Setting] Parameter Numbe
B-66 Parameters 1503-UM054C-EN-P – June 2013 Table B.24 – Drop Out Time Settings from IB2 DIP Switches Value Enum Text Description 0 50 ms 50
Parameters B-67 1503-UM054C-EN-P – June 2013 Drop Out Time Setting From IB4 DIP Switches [IB 4 Drop Out Time DIP Setting] Parameter Numbe
B-68 Parameters 1503-UM054C-EN-P – June 2013 Table B.27 – Drop Out Time Settings From IB5 DIP Switches Value Enum Text Description 0 50 ms 50
Parameters B-69 1503-UM054C-EN-P – June 2013 Contactor Pick Up Time for IB3 [IB 3 Pick Up Time] Parameter Number: 125,107,89,_,_. Acces
B-70 Parameters 1503-UM054C-EN-P – June 2013 Contactor Pick Up Time for IB5 [IB 5 Pick Up Time] Parameter Number: 127,_,_,_,_. Access rule:
Parameters B-71 1503-UM054C-EN-P – June 2013 TDUV Time Setting from IB2 DIP Switches [IB 2 TDUV Time DIP Setting] Parameter Number: 129
B-72 Parameters 1503-UM054C-EN-P – June 2013 Table B.30 – TDUV Time Setting From I B3 DIP Switches Value Enum Text Description 0 0.2 Sec 0.2 S
Parameters B-73 1503-UM054C-EN-P – June 2013 TDUV Time Setting from IB5 DIP Switches [IB 5 TDUV Time DIP Setting] Parameter Number: 132
B-74 Parameters 1503-UM054C-EN-P – June 2013 TDUV Time Setting for IB2 [IB 2 TDUV Time] Parameter Number: 134,114,94,74,_. Access rule: Ge
3-2 Installation 1503-UM054C-EN-P – June 2013 Arrangements The IntelliVAC is offered in two arrangements, Integral (part of a Bulletin 1500
Parameters B-75 1503-UM054C-EN-P – June 2013 TDUV Time Setting for IB4 [IB 4 TDUV Time] Parameter Number: 136,116,_,_,_. Access rule:
B-76 Parameters 1503-UM054C-EN-P – June 2013 Delay Restart Time for IB1 [IB 1 Delay Restart Time] Parameter Number: 138,117,96,75,53. Access
Parameters B-77 1503-UM054C-EN-P – June 2013 Delay Restart Time for IB3 [IB 3 Delay Restart Time] Parameter Number: 140,119,98,_,_. Acc
B-78 Parameters 1503-UM054C-EN-P – June 2013 Delay Restart Time for IB5 [IB 5 Delay Restart Time] Parameter Number: 142,_,_,_,_. Access rule:
Parameters B-79 1503-UM054C-EN-P – June 2013 Delay Restart Wait Time for IB2 [IB 2 Delay Restart Wait Time] Parameter Number: 144,122,1
B-80 Parameters 1503-UM054C-EN-P – June 2013 Delay Restart Wait Time for IB4 [IB 4 Delay Restart Wait Time] Parameter Number: 146,124,_,_,_.
Parameters B-81 1503-UM054C-EN-P – June 2013 Jog Time for IB1 [IB 1 Jog Time] Parameter Number: 148,125,102,79,55. Access rule: Get/S
B-82 Parameters 1503-UM054C-EN-P – June 2013 Jog Time for IB3 [IB 3 Jog Time] Parameter Number: 150,127,104,_,_. Access rule: Get/Set Data
Parameters B-83 1503-UM054C-EN-P – June 2013 Jog Time for IB5 [IB 5 Jog Time] Parameter Number: 152,_,_,_,_. Access rule: Get/Set Dat
B-84 Parameters 1503-UM054C-EN-P – June 2013 Jog Repetition Time for IB2 [IB 2 Jog Repetition Time] Parameter Number: 154,130,106,82,_. Acces
Installation 3-3 1503-UM054C-EN-P – June 2013 Figure 3.2 – Typical Mounting Configurations Note: Adjacent IntelliVAC modules ma
Parameters B-85 1503-UM054C-EN-P – June 2013 Jog Repetition Time for IB4 [IB 4 Jog Repetition Time] Parameter Number: 156,132,_,_,_. A
B-86 Parameters 1503-UM054C-EN-P – June 2013 Diagnostics Parameters Invalid Command on IB1 Level [IB 1 Invalid Command] Parameter Number: 15
Parameters B-87 1503-UM054C-EN-P – June 2013 Invalid Command on IB3 Level [IB 3 Invalid Command] Parameter Number: 160,135,110,_,_. Ac
B-88 Parameters 1503-UM054C-EN-P – June 2013 Invalid Command on IB5 Level [IB 5 Invalid Command] Parameter Number: 162,_,_,_,_. Access rule:
Parameters B-89 1503-UM054C-EN-P – June 2013 Mechanical Latch Fails to Trip on IB2 [IB 2 Mechanical Latch Fail to Trip] Parameter Number
B-90 Parameters 1503-UM054C-EN-P – June 2013 Mechanical Latch Fails to Trip on IB4 [IB 4 Mechanical Latch Fail to Trip] Parameter Number: 16
Parameters B-91 1503-UM054C-EN-P – June 2013 Contactor Fails to Pick-Up on IB1 [IB 1 Contactor Fails to Pick-Up] Parameter Number: 168
B-92 Parameters 1503-UM054C-EN-P – June 2013 Contactor Fails to Pick-Up on IB3 [IB 3 Contactor Fails to Pick-Up] Parameter Number: 170,143,1
Parameters B-93 1503-UM054C-EN-P – June 2013 Contactor Fails to Pick-Up on IB5 [IB 5 Contactor Fails to Pick-Up] Parameter Number: 172
B-94 Parameters 1503-UM054C-EN-P – June 2013 Contactor Drop-Out during Hold on IB2 [IB 2 Contactor Drop-out During Hold] Parameter Number: 1
3-4 Installation 1503-UM054C-EN-P – June 2013 It is recommended the user interface with the IntelliVAC Plus using interposing relays if po
Parameters B-95 1503-UM054C-EN-P – June 2013 Contactor Drop-Out during Hold on IB4 [IB 4 Contactor Drop-out During Hold] Parameter Numbe
B-96 Parameters 1503-UM054C-EN-P – June 2013 Contactor Long Drop Out Time on IB1 [IB 1 Contactor Long Drop Out Time] Parameter Number: 178,1
Parameters B-97 1503-UM054C-EN-P – June 2013 Contactor Long Drop Out Time on IB3 [IB 3 Contactor Long Drop Out Time] Parameter Number:
B-98 Parameters 1503-UM054C-EN-P – June 2013 Contactor Long Drop Out Time on IB5 [IB 5 Contactor Long Drop Out Time] Parameter Number: 182,_
Parameters B-99 1503-UM054C-EN-P – June 2013 Contactor Fails to Drop Out on IB2 [IB 2 Contactor Fails To Drop Out] Parameter Number: 1
B-100 Parameters 1503-UM054C-EN-P – June 2013 Contactor Fails to Drop Out on IB4 [IB 4 Contactor Fails To Drop Out] Parameter Number: 186,15
Parameters B-101 1503-UM054C-EN-P – June 2013 Long Close Time on IB1 [IB 1 Long Close Time] Parameter Number: 188,157,126,95,63. Access
B-102 Parameters 1503-UM054C-EN-P – June 2013 Long Close Time on IB3 [IB 3 Long Close Time] Parameter Number: 190,159,128,_,_. Access rule:
Parameters B-103 1503-UM054C-EN-P – June 2013 Long Close Time on IB5 [IB 5 Long Close Time] Parameter Number: 192,_,_,_,_. Access rule:
B-104 Parameters 1503-UM054C-EN-P – June 2013 Power Up with Contactor Closed on IB2 [IB 2 Power-up with Contactor Closed] Parameter Number:
Chapter 4 1503-UM054C-EN-P – June 2013 Description of Features The IntelliVAC Plus incorporates a TDUV feature, which will keep the contac
Parameters B-105 1503-UM054C-EN-P – June 2013 Power Up with Contactor Closed on IB4 [IB 4 Power-up with Contactor Closed] Parameter Numb
B-106 Parameters 1503-UM054C-EN-P – June 2013 Power Up with Invalid DIP Switch Configuration on IB1 [IB 1 Power-up with Invalid DIP Switch Conf
Parameters B-107 1503-UM054C-EN-P – June 2013 Power Up with Invalid DIP Switch Configuration on IB3 [IB 3 Power-up with Invalid DIP Switc
B-108 Parameters 1503-UM054C-EN-P – June 2013 Power Up with Invalid DIP Switch Configuration on IB5 [IB 5 Power-up with Invalid DIP Switch Conf
Parameters B-109 1503-UM054C-EN-P – June 2013 Under Voltage with Close Command Present on IB2 [IB 2 U/V with Close Command Present] Para
B-110 Parameters 1503-UM054C-EN-P – June 2013 Under Voltage with Close Command Present on IB4 [IB 4 U/V with Close Command Present] Parameter
Parameters B-111 1503-UM054C-EN-P – June 2013 Module not Healthy on IB1 [IB 1 Module not Healthy] Parameter Number: 208,173,138,103,67.
B-112 Parameters 1503-UM054C-EN-P – June 2013 Module not Healthy on IB3 [IB 3 Module not Healthy] Parameter Number: 210,175,140,_,_. Access r
Parameters B-113 1503-UM054C-EN-P – June 2013 Module not Healthy on IB5 [IB 5 Module not Healthy] Parameter Number: 212,_,_,_,_. Access
B-114 Parameters 1503-UM054C-EN-P – June 2013 Contactor not Healthy on IB3 [IB 3 Contactor Not Healthy] Parameter Number: 215,179,143,_,_. Acc
4-2 Description of Features 1503-UM054C-EN-P – June 2013 TDUV Programmability With the IntelliVAC Plus unit TDUV settings w ill be altered
Parameters B-115 1503-UM054C-EN-P – June 2013 Input Line Undervoltage during Close on IB1 [IB 1 Line Undervoltage Close] Parameter Numbe
B-116 Parameters 1503-UM054C-EN-P – June 2013 Input Line Undervoltage During Close on IB3 [IB 3 Line Undervoltage Close] Parameter Number: 2
Parameters B-117 1503-UM054C-EN-P – June 2013 Input Line Undervoltage during Close on IB5 [IB 5 Line Undervoltage Close] Parameter Numbe
B-118 Parameters 1503-UM054C-EN-P – June 2013 Input Line Undervoltage during Hold on IB2 [IB 2 Line Undervoltage Hold] Parameter Number: 224
Parameters B-119 1503-UM054C-EN-P – June 2013 Input Line Undervoltage during Hold on IB4 [IB 4 Line Undervoltage Hold Parameter Number:
B-120 Parameters 1503-UM054C-EN-P – June 2013 Input Line Overvoltage on IB1 [IB 1 Line Overvoltage] Parameter Number: 228,189,150,111,71. Acc
Parameters B-121 1503-UM054C-EN-P – June 2013 Input Line Overvoltage on IB3 [IB 3 Line Overvoltage] Parameter Number: 230,191,152,_,_.
B-122 Parameters 1503-UM054C-EN-P – June 2013 Input Line Overvoltage on IB5 [IB 5 Line Overvoltage] Parameter Number: 232,_,_,_,_. Access ru
Parameters B-123 1503-UM054C-EN-P – June 2013 Loss of Input Line Power on IB2 [IB 2 Line Loss] Parameter Number: 234,194,154,114,_. Acce
B-124 Parameters 1503-UM054C-EN-P – June 2013 Loss of Input Line Power on IB5 [IB 5 Line Loss] Parameter Number: 237,_,_,_,_. Access rule:
Table of Contents 1503-UM054C-EN-P – June 2013 Chapter 1 Product Description Introduction ...
Description of Features 4-3 1503-UM054C-EN-P – June 2013 ‘I B1 TDUV time DIP setting = ‘‘0.2’ or ‘0.500’ or ‘1.000’ or ‘2.000’ ‘Sec’
Parameters B-125 1503-UM054C-EN-P – June 2013 Main Coil Open on IB3 [IB 3 Main Coil Open] Parameter Number: 240,199,158,_,_. Access rule
B-126 Parameters 1503-UM054C-EN-P – June 2013 Trip Coil Open on IB1 [IB 1 Trip Coil Open] Parameter Number: 243,201,159,117,74. Access rule:
Parameters B-127 1503-UM054C-EN-P – June 2013 Trip Coil Open on IB4 [IB 4 Trip Coil Open] Parameter Number: 246,204,_,_,_. Access rule:
B-128 Parameters 1503-UM054C-EN-P – June 2013 Extended Close Time on IB2 [IB 2 Extended Pick up Time] Parameter Number: 249,206,163,120,_. A
Parameters B-129 1503-UM054C-EN-P – June 2013 Extended Close Time on IB4 [IB 4 Extended Pick up Time] Parameter Number: 251,208,_,_,_.
B-130 Parameters 1503-UM054C-EN-P – June 2013 Average Number of Operations per Time Unit on IB1 [IB 1 Average Operations per Time Unit] Parame
Parameters B-131 1503-UM054C-EN-P – June 2013 Average Number of Operations per Time Unit on IB2 [IB 2 Average Operations per Time Unit]
B-132 Parameters 1503-UM054C-EN-P – June 2013 Average Number of Operations per Time Unit on IB3 [IB 3 Average Operations per Time Unit] Parame
Parameters B-133 1503-UM054C-EN-P – June 2013 Average Number of Operations per Time Unit on IB4 [IB 4 Average Operations per Time Unit]
B-134 Parameters 1503-UM054C-EN-P – June 2013 Average Number of Operations per Time Unit on IB5 [IB 5 Average Operations per Time Unit] Parame
4-4 Description of Features 1503-UM054C-EN-P – June 2013 ‘IB1 Drop-Out Time = ‘ ’50 mSec’ to ‘240 mSec’ (resolution is 1mS) ‘I B2 Drop-
Parameters B-135 1503-UM054C-EN-P – June 2013 Total Number of Close Operations on IB1 [IB 1 Master Counter] Parameter Number: 263,217,
B-136 Parameters 1503-UM054C-EN-P – June 2013 Total Number of Close Operations on IB3 [IB 3 Master Counter] Parameter Number: 265,219,173,_,
Parameters B-137 1503-UM054C-EN-P – June 2013 Total Number of Close Operations on IB5 [IB 5 Master Counter] Parameter Number: 267,_,_,
B-138 Parameters 1503-UM054C-EN-P – June 2013 highest level will contain the data that was in the second highest level. This system will prov
Parameters B-139 1503-UM054C-EN-P – June 2013 Average Number of Operations per Time Unit on IB3 [IB 3 Reset Operations Since Counter] Pa
B-140 Parameters 1503-UM054C-EN-P – June 2013 Average Number of Operations per Time Unit on IB4 [IB 4 Reset Operations Since Counter] Paramete
Parameters B-141 1503-UM054C-EN-P – June 2013 Average Number of Operations per Time Unit on IB5 [IB 5 Reset Operations Since Counter] Pa
B-142 Parameters 1503-UM054C-EN-P – June 2013 Operations since 0 Count Value on IB1 [IB 1 Operations Since 0 Count Value] Parameter Number:
Parameters B-143 1503-UM054C-EN-P – June 2013 Time of Operations Since 0 Count Value on IB1 [IB 1 Operations since 0 Time] Parameter Num
B-144 Parameters 1503-UM054C-EN-P – June 2013 Date of Operations Since 1 Count Value on IB1 [IB 1 Operations Since 1 Date] Parameter Number:
Description of Features 4-5 1503-UM054C-EN-P – June 2013 Time. If the contactor did not close within 200mS then there is a major problem
Parameters B-145 1503-UM054C-EN-P – June 2013 Operations Since 2 Count Value on IB1 [IB 1 Operations Since 2 Count Value] Parameter Numb
B-146 Parameters 1503-UM054C-EN-P – June 2013 Time of Operations Since 2 Count Value on IB1 [IB 1 Operations Since 2 Time] Parameter Number:
Parameters B-147 1503-UM054C-EN-P – June 2013 Date of Operations Since 0 Count Value on IB2 [IB 2 Operations Since 0 Date] Parameter Num
B-148 Parameters 1503-UM054C-EN-P – June 2013 Operations Since 1 Count Value on IB2 [IB 2 Operations Since 1 Count Value] Parameter Number:
Parameters B-149 1503-UM054C-EN-P – June 2013 Time of Operations Since 1 Count Value on IB2 [IB 2 Operations Since 1 Time] Parameter Num
B-150 Parameters 1503-UM054C-EN-P – June 2013 Date of Operations Since 2 Count Value on IB2 [IB 2 Operations Since 2 Date] Parameter Number:
Parameters B-151 1503-UM054C-EN-P – June 2013 Operations Since 0 Count Value on IB3 [IB 3 Operations Since 0 Count Value] Parameter Numb
B-152 Parameters 1503-UM054C-EN-P – June 2013 Time of Operations Since 0 Count Value on IB3 [IB 3 Operations Since 0 Time] Parameter Number:
Parameters B-153 1503-UM054C-EN-P – June 2013 Date of Operations Since 1 Count Value on IB3 [IB 3 Operations Since 1 Date] Parameter Num
B-154 Parameters 1503-UM054C-EN-P – June 2013 Operations Since 2 Count Value on IB3 [IB 3 Operations Since 2 Count Value] Parameter Number:
4-6 Description of Features 1503-UM054C-EN-P – June 2013 Delayed Restart (General) The contactors are assigned rated duties, which define ho
Parameters B-155 1503-UM054C-EN-P – June 2013 Time of Operations Since 2 Count Value on IB3 [IB 3 Operations Since 2 Time] Parameter Num
B-156 Parameters 1503-UM054C-EN-P – June 2013 Date of Operations Since 0 Count Value on IB4 [IB 4 Operations Since 0 Date] Parameter Number:
Parameters B-157 1503-UM054C-EN-P – June 2013 Operations Since 1 Count Value on IB4 [IB 4 Operations Since 1 Count Value] Parameter Numb
B-158 Parameters 1503-UM054C-EN-P – June 2013 Time of Operations Since 1 Count Value on IB4 [IB 4 Operations Since 1 Time] Parameter Number:
Parameters B-159 1503-UM054C-EN-P – June 2013 Date of Operations Since 2 Count Value on IB4 [IB 4 Operations Since 2 Date] Parameter Num
B-160 Parameters 1503-UM054C-EN-P – June 2013 Operations Since 0 Count Value on IB5 [IB 5 Operations Since 0 Count Value] Parameter Number:
Parameters B-161 1503-UM054C-EN-P – June 2013 Time of Operations Since 0 Count Value on IB5 [IB 5 Operations Since 0 Time] Parameter Num
B-162 Parameters 1503-UM054C-EN-P – June 2013 Date of Operations Since 1 Count Value on IB5 [IB 5 Operations Since 1 Date] Parameter Number:
Parameters B-163 1503-UM054C-EN-P – June 2013 Operations Since 2 Count Value on IB5 [IB 5 Operations Since 2 Count Value] Parameter Numb
B-164 Parameters 1503-UM054C-EN-P – June 2013 Time of Operations Since 2 Count Value on IB5 [IB 5 Operations Since 1 Time] Parameter Number:
Description of Features 4-7 1503-UM054C-EN-P – June 2013 ‘IB3 Delay Restart Wait Time = ‘ ‘x Sec’ (Note: This value, as it is being v
Parameters B-165 1503-UM054C-EN-P – June 2013 Length of Event Log on IB2 [IB 2 Event Present Length] Parameter Number: 319,262,205,148
B-166 Parameters 1503-UM054C-EN-P – June 2013 Length of Event Log on IB4 [IB 4 Event Present Length] Parameter Number: 321,264,_,_,_. Access
Parameters B-167 1503-UM054C-EN-P – June 2013 Module Status of IB1 [IB Status] Parameter Number: 323,265,207,149,90. Access rule: Ge
B-168 Parameters 1503-UM054C-EN-P – June 2013 Invalid DeviceLogix Program Loaded [Invalid DeviceLogix Program] Parameter Number: 325,267,209
Parameters B-169 1503-UM054C-EN-P – June 2013 Altitude Settings on MC Units Inconsistent [MC Altitude Set Warning] Parameter Number: 3
B-170 Parameters 1503-UM054C-EN-P – June 2013 Drop Out Time Source [Drop Out Time Source] Parameter Number: 329,271,213,155,96. Access rule:
Parameters B-171 1503-UM054C-EN-P – June 2013 Contactor Coil Current for IB2 [IB 2 Contactor Coil Current] Parameter Number: 331,273,2
B-172 Parameters 1503-UM054C-EN-P – June 2013 Contactor Coil Current for IB4 [IB 4 Contactor Coil Current] Parameter Number: 333,275,_,_,_.
Parameters B-173 1503-UM054C-EN-P – June 2013 Status Word for IB1 [IB 1 Status Word] Parameter Number: 335,276,217,158,98. Access rule:
B-174 Parameters 1503-UM054C-EN-P – June 2013 Status Word for IB2 [IB 2 Status Word] Parameter Number: 336,277,218,159,_. Access rule: Get
4-8 Description of Features 1503-UM054C-EN-P – June 2013 Counters must be implemented to keep track of the Jog time as well as for the Jog Re
Parameters B-175 1503-UM054C-EN-P – June 2013 Status Word for IB3 [IB 3 Status Word] Parameter Number: 337,278,219,_,_. Access rule:
B-176 Parameters 1503-UM054C-EN-P – June 2013 Status Word for IB4 [IB 4 Status Word] Parameter Number: 338,279,_,_,_. Access rule: Get Dat
Parameters B-177 1503-UM054C-EN-P – June 2013 Status Word for IB5 [IB 5 Status Word] Parameter Number: 339,_,_,_,_. Access rule: Get
B-178 Parameters 1503-UM054C-EN-P – June 2013 Correct Termination Resistor Installed in MC System [Correct MC Termination Resistor] Parameter
Parameters B-179 1503-UM054C-EN-P – June 2013 Termination Resistor Installed in IB3 [IB3 Termination Resistor] Parameter Number: 342,2
B-180 Parameters 1503-UM054C-EN-P – June 2013 Termination Resistor Installed in IB5 [IB5 Termination Resistor] Parameter Number: 344,_,_,_,_.
Parameters B-181 1503-UM054C-EN-P – June 2013 Status Word for the MC System [MC System Status] Parameter Number: 346,285,224,163,101.
B-182 Parameters 1503-UM054C-EN-P – June 2013 MC System Ready Status [MC System Ready Status] Parameter Number: 347,286,225,164,102. Ac c es
Parameters B-183 1503-UM054C-EN-P – June 2013 MC System Locked [MC System Locked] Parameter Number: 349,288,227,166,104. Access rule:
B-184 Parameters 1503-UM054C-EN-P – June 2013 IB1 Firmware Version [IB1 Firmware Version] Parameter Number: 351,290,229,168,106. Access rule:
Description of Features 4-9 1503-UM054C-EN-P – June 2013 Items #30 to #49, in the Event Log, which apply to the DeviceLogix I/O, will on
Parameters B-185 1503-UM054C-EN-P – June 2013 IB4 Firmware Version [IB4 Firmware Version] Parameter Number: 354,293,_,_,_. Access rule:
B-186 Parameters 1503-UM054C-EN-P – June 2013
Appendix C 1503-UM054C-EN-P – June 2013 Maintenance Introduction The IntelliVAC Plus product has is a very robust device which contains only
C-2 Maintenance 1503-UM054C-EN-P – June 2013 I M P O R T A N TI M P O R T A N T The cause of the fuse failure should be identified before the fu
Appendix D 1503-UM054C-EN-P – June 2013 Spare Parts Table D.1 – Spare Parts Item Description Part Number Internal Fuse 6.3A, 250V (Little
D-2 Spare Parts 1503-UM054C-EN-P – June 2013
Appendix E 1503-UM054C-EN-P – June 2013 DeviceNet Information Identify Object Table E.1 - Class Attributes Attribute ID Access Rule Name Devi
E-2 DeviceNet Information 1503-UM054C-EN-P – June 2013 Table E.3 – Device Status Bit No. Status Data Value Bit 0 Owned 0=not owned 1=owned
DeviceNet Information E-3 1503-UM054C-EN-P – June 2013 Table E.6 – Instance Attributes Attribute ID Access Rule Name DeviceNet Data T
E-4 DeviceNet Information 1503-UM054C-EN-P – June 2013 Explicit Connection Table E.9 - Instance Attributes (predefined slave explicit connection)
4-10 Description of Features 1503-UM054C-EN-P – June 2013 Table 4.D – Event Log Data (cont.) Event Code Data Time Stamp OUTA Close 46 None “
DeviceNet Information E-5 1503-UM054C-EN-P – June 2013 Parameter Object The parameter object and parameter object are all for mainly fo
E-6 DeviceNet Information 1503-UM054C-EN-P – June 2013 Common Service Table E.12 - Service Codes Service Code Implementation for Service Name
DeviceNet Information E-7 1503-UM054C-EN-P – June 2013 Output (Consumed) Assembly and Layout Output assembly instances attribute and fo
E-8 DeviceNet Information 1503-UM054C-EN-P – June 2013 Input (Produced) Assembly and Layout Table E.17 – Input assembly instances attribute and
DeviceNet Information E-9 1503-UM054C-EN-P – June 2013 Important Notes: *About PNBnn/IBx-Outy: this is IntelliVAC ass embly’s unique f
E-10 DeviceNet Information 1503-UM054C-EN-P – June 2013 Table E.22 – Instance Attributes Attribute ID Access Rule Attribute Name Data Type Defa
DeviceNet Information E-11 1503-UM054C-EN-P – June 2013 Table E.22 – Instance Attributes (cont.) Attribute ID Access Rule Attribute Nam
E-12 DeviceNet Information 1503-UM054C-EN-P – June 2013 Table E.25 - Instance Attribute Parameter No. Control Parameter Access Rule Type Descripti
DeviceNet Information E-13 1503-UM054C-EN-P – June 2013 Table E.25 - Instance Attribute (cont.) Parameter No. Control Parameter Access Ru
E-14 DeviceNet Information 1503-UM054C-EN-P – June 2013 Table E.25 - Instance Attribute (cont.) Parameter No. Control Parameter Access Rule Type
Description of Features 4-11 1503-UM054C-EN-P – June 2013 Coil Currents The coil currents represent the average value of the particular
DeviceNet Information E-15 1503-UM054C-EN-P – June 2013 PCP Object (Motor Control Center Object) Class Attributes: None Number of Insta
E-16 DeviceNet Information 1503-UM054C-EN-P – June 2013 Data Table Layout Table E.29 shows the data table layout. Table E.29 – DeviceLogix Data
DeviceNet Information E-17 1503-UM054C-EN-P – June 2013 Table E.29 – DeviceLogix Data Table Layout (cont.) Byte Bit 7 Bit 6 Bit 5 B
E-18 DeviceNet Information 1503-UM054C-EN-P – June 2013
Appendix F 1503-UM054C-EN-P – June 2013 IntelliVAC Plus Firmware Introduction In order to update the firmware of the IntelliVAC Plus module
F-2 IntelliVAC Plus Firmware 1503-UM054C-EN-P – June 2013 • Configure the selected DeviceNet driver Figure F.2 – DeviceNet Drive Configura
Medium Voltage Products, 135 Dundas Street, Cambridge, ON, N1R 5X1 Canada, Tel: (1) 519.740.4100, Fax: (1)
4-12 Description of Features 1503-UM054C-EN-P – June 2013 Open Coil Test To check that there is a coil(s) connected to the IntelliVAC Plus
ii Table of Contents 1503-UM054C-EN-P – June 2013 Chapter 4 Description of Features (cont.) Supply Voltages ...
Description of Features 4-13 1503-UM054C-EN-P – June 2013 Supply Voltages The AC and DC supply voltage measurements represent the RMS
4-14 Description of Features 1503-UM054C-EN-P – June 2013 The ‘I Bx Line Undervoltage’ and ‘I Bx Line Undervoltage’ values are included to a
Description of Features 4-15 1503-UM054C-EN-P – June 2013 Time Zone Selection To facilitate in the setting of the time of day for diffe
4-16 Description of Features 1503-UM054C-EN-P – June 2013 The IntelliVAC Plus is adaptable to a range of atmospheric pressures and altitudes
Description of Features 4-17 1503-UM054C-EN-P – June 2013 “Master” Counter The Master c ounter w ill inc lude all operations, since
4-18 Description of Features 1503-UM054C-EN-P – June 2013 ‘I B2 Reset Ops Since Counter’ (present ‘IB2 Ops Since 0 data/time’ saved to ‘IB2
Description of Features 4-19 1503-UM054C-EN-P – June 2013 ‘IB3 Operation Since 0 Count Value =’ ‘0’ to ‘16777215’ 24 bit counter) ‘
4-20 Description of Features 1503-UM054C-EN-P – June 2013 “Average Operations” Counter The Average Operations counter will include Average
Description of Features 4-21 1503-UM054C-EN-P – June 2013 Configuration The IntelliVAC Plus Unit will be configured in one of two
4-22 Description of Features 1503-UM054C-EN-P – June 2013 In an MC system all MC operation will cease and communications between the various
Table of Contents iii 1503-UM054C-EN-P – June 2013 Chapter 4 Description of Features (cont.) Network Status (DeviceNet)...
Description of Features 4-23 1503-UM054C-EN-P – June 2013 Table 4.E – IB Fault/Warning Descriptions IntelliVAC Status Indication (Series
4-24 Description of Features 1503-UM054C-EN-P – June 2013 The Contactor status LED is off to indicate that the contactor is in an Open condit
Description of Features 4-25 1503-UM054C-EN-P – June 2013 Close, Jog or Trip commands are present during a power on sequence.
4-26 Description of Features 1503-UM054C-EN-P – June 2013 Note: Close and Jog are for an Electrically Held contactor and Close and Trip are
Description of Features 4-27 1503-UM054C-EN-P – June 2013 This is a Fault condition and the IntelliVAC Plus will not respond to other
4-28 Description of Features 1503-UM054C-EN-P – June 2013 Contactor Drop Out During Hold This is a Warning condition and the status of the c
Description of Features 4-29 1503-UM054C-EN-P – June 2013 Microcontroller Malfunction This is a serious Fault condition and the Intelli
4-30 Description of Features 1503-UM054C-EN-P – June 2013 Contactor Fails to Drop Out This is a Fault condition and the IntelliVAC Plus wil
Description of Features 4-31 1503-UM054C-EN-P – June 2013 The Contactor status LED is off to indicate that the contactor is in an Open c
4-32 Description of Features 1503-UM054C-EN-P – June 2013 This condition is valid for both Electrically Held and Mechanically Latched conta
iv Table of Contents 1503-UM054C-EN-P – June 2013 Chapter 6 Wiring Wiring (MC) ...
Description of Features 4-33 1503-UM054C-EN-P – June 2013 Table 4.F - Plus Fault/Warning Description Fault/Warning Red LED Green LED
4-34 Description of Features 1503-UM054C-EN-P – June 2013 When a fault/warning occurs, the appropriate LED will flash and the appropriate fau
Description of Features 4-35 1503-UM054C-EN-P – June 2013 Programming Base Unit(s) This is a Normal firmware flashing condition and no
4-36 Description of Features 1503-UM054C-EN-P – June 2013 Line Undervoltage This is a Warning condition which may not be rectified by the us
Description of Features 4-37 1503-UM054C-EN-P – June 2013 Table 4.G – Contactor Extended Close Times CONTACTOR CONFIGURATION @ Vinput Ma
4-38 Description of Features 1503-UM054C-EN-P – June 2013 MC Altitude Setting Warning This is a Warning condition which indicates that the
Description of Features 4-39 1503-UM054C-EN-P – June 2013 Application Programming Error – CRC This is a Fault c ondition which indica
4-40 Description of Features 1503-UM054C-EN-P – June 2013 There is a Red/Green bi-c olor LED which is used to indicate the DeviceNet network
Description of Features 4-41 1503-UM054C-EN-P – June 2013 IE Determining Network Baud Rate The DeviceNet status LED is flashing Green.
4-42 Description of Features 1503-UM054C-EN-P – June 2013 Table 4.I – DeviceNet Module Status LED Fault/Warning Red LED Green LED Descript
Table of Contents v 1503-UM054C-EN-P – June 2013 Chapter 8 Configurations (cont.) MC RS485 Addressing ...
Description of Features 4-43 1503-UM054C-EN-P – June 2013 The DeviceNet status LED is solid Green.
4-44 Description of Features 1503-UM054C-EN-P – June 2013 Recoverable Fault This is a Warning condition and indicates that the IntelliVAC P
Description of Features 4-45 1503-UM054C-EN-P – June 2013 For the 7-segment LED display, the ‘Watchdog Timeout’ and the ‘System Lock-Out
4-46 Description of Features 1503-UM054C-EN-P – June 2013 MC Bad MC #1 This is a Fault condition and indicates that the IntelliVAC MC #1, wh
Description of Features 4-47 1503-UM054C-EN-P – June 2013 See Table 8.K for a definition of w hic h IntelliVAC unit is to have the term
4-48 Description of Features 1503-UM054C-EN-P – June 2013 The 7-segment display will display the flashing character ‘7’ + ‘Dec imal Point’.
Chapter 5 1503-UM054C-EN-P – June 2013 IntelliVAC Plus Basic Wiring Fuse Protection The IntelliVAC module requires external fuse protection
5-2 IntelliVAC Plus Basic Wiring 1503-UM054C-EN-P – June 2013 Grounding The IntelliVAC module must be connected to a common ground terminal
IntelliVAC Plus Basic Wiring 5-3 1503-UM054C-EN-P – June 2013 Interface Connections Further control interface connections are made at a
5-4 IntelliVAC Plus Basic Wiring 1503-UM054C-EN-P – June 2013 When configured for basic control the IntelliVAC Plus can be applied with t
vi Table of Contents 1503-UM054C-EN-P – June 2013 Chapter 9 DeviceLogix (cont.) Up Down Counter...
IntelliVAC Plus Basic Wiring 5-5 1503-UM054C-EN-P – June 2013 A T T E N T I O NA T T E N T I O N For Emergency Stop applications requiri
5-6 IntelliVAC Plus Basic Wiring 1503-UM054C-EN-P – June 2013 MOV321EC-+4TCO1211AUX CCO56L1 L2/NG+ -STOPSTARTOVERLOADCONTROLPOWERFUSE*M-IV9 1
IntelliVAC Plus Basic Wiring 5-7 1503-UM054C-EN-P – June 2013 IntelliVAC control may be used for mechanical latch contactors. A mome
5-8 IntelliVAC Plus Basic Wiring 1503-UM054C-EN-P – June 2013 Capacitor Trip The IntelliVAC can be configured to provide capacitor trip
IntelliVAC Plus Basic Wiring 5-9 1503-UM054C-EN-P – June 2013 MOV321EC-+4TCO1211AUX CCO56L1 L2/NG+ -CLOSEOVERLOADCONTROLPOWERFUSE*CONTR
5-10 IntelliVAC Plus Basic Wiring 1503-UM054C-EN-P – June 2013 Table 5.D – Maximum TDUV Time (without Capacitor) Control Voltage Max. TD
IntelliVAC Plus Basic Wiring 5-11 1503-UM054C-EN-P – June 2013 Figure 5.9 – Wiring Diagram for
5-12 IntelliVAC Plus Basic Wiring 1503-UM054C-EN-P – June 2013 Figure 5.10 – Wiring Diagram for Full Voltage Non-Reversing Logic M
Chapter 6 1503-UM054C-EN-P – June 2013 Wiring Wiring (MC) Pre Configured Logic Mode The IntelliVAC Plus comes with five
6-2 Wiring (MC) 1503-UM054C-EN-P – June 2013 Wiring (MC) (cont.) After selecting the desired control program, the IntelliVAC Plus module mu
Table of Contents vii 1503-UM054C-EN-P – June 2013 Appendix D Spare Parts ...
Wiring (MC) 6-3 1503-UM054C-EN-P – June 2013 Figure 6.2 – Wiring Diagram for Full Voltage Reversing Configuration Required: • Gate
6-4 Wiring (MC) 1503-UM054C-EN-P – June 2013 Figure 6.3 – Wiring Diagram for SMC This circuit is set up for Soft Start or Current Limit
Wiring (MC) 6-5 1503-UM054C-EN-P – June 2013 Figure 6.4 – Wiring Diagram for SMC (cont.) Configuration Required: None This ci
6-6 Wiring (MC) 1503-UM054C-EN-P – June 2013 Figure 6.5 – Wiring Diagram for SMC with PFCC This circuit is set up for Soft Start or Curr
Wiring (MC) 6-7 1503-UM054C-EN-P – June 2013 Figure 6.6 – Wiring Diagram for SMC with PFCC (cont.) Configuration Required: None
6-8 Wiring (MC) 1503-UM054C-EN-P – June 2013 Figure 6.7 – Wiring Diagram for Reduced Voltage Reactor RVR Configuration Required: • Gate 2
Wiring (MC) 6-9 1503-UM054C-EN-P – June 2013 Incomplete Sequence Timer The Incomplete sequence timer is designed to ensure that the du
6-10 Wiring (MC) 1503-UM054C-EN-P – June 2013 Figure 6.8 – Wiring Diagram for Reduced Voltage Auto Transformer RVAT Configuration Requir
Wiring (MC) 6-11 1503-UM054C-EN-P – June 2013 Incomplete Sequence Timer The Incomplete sequence timer is designed to ensure that the d
6-12 Wiring (MC) 1503-UM054C-EN-P – June 2013