Parameters B-161
1503-UM054C-EN-P June 2013
Time of Operations Since 0 Count Value on IB5
[IB 5 Operations Since 0 Time]
Parameter Number: 311,_,_,_,_.
Access rule: Get
Data Type: TIME
Object Mapping: 0x384-5-36
Group: Diagnostics
Units : -
Minimum Value: 0
Maximum Value: 0xFFFF
Default Value: 0
This parameter allows the user to view the Time for which the
Operations since a Reset Counter on IB5 event occurred. See
“Operations Since” Counter in Chapter 4 for a more detailed
description of this feature.
Operations Since 1 Count Value on IB5
[IB 5 Operations Since 1 Count Value]
Parameter Number: 312,_,_,_,_.
Access rule: Get
Data Type: UDINT
Object Mapping: 0x384-5-37
Group: Diagnostics
Units : -
Minimum Value: 0
Maximum Value: 0xFFFFFF
Default Value: 0
This parameter allows the user to view the number of Operations
since a Reset Counter on IB5 event occurred and transferred the
Since 0 count value to the Since 1 count value. See “Operations
Since” Counter in Chapter 4 for a more detailed description of this
feature.