Parameters B-157
1503-UM054C-EN-P June 2013
Operations Since 1 Count Value on IB4
[IB 4 Operations Since 1 Count Value]
Parameter Number: 303,255,_,_,_.
Access rule: Get
Data Type: UDINT
Object Mapping: 0x384-4-37
Group: Diagnostics
Units : -
Minimum Value: 0
Maximum Value: 0xFFFFFF
Default Value: 0
This parameter allows the user to view the number of Operations
since a Reset Counter on IB4 event occurred and transferred the
Since 0 count value to the Since 1 count value. See “Operations
Sinc e Counter in Chapter 4 for a more detailed description of this
feature.
Date of Operations Since 1 Count Value on IB4
[IB 4 Operations Since 1 Date]
Parameter Number: 304,256,_,_,_.
Access rule: Get
Data Type: DATE
Object Mapping: 0x384-4-38
Group: Diagnostics
Units : -
Minimum Value: 0
Maximum Value: 0xFFFF
Default Value: 0
This parameter allows the user to view the Date for which the
Operations since a Reset Counter on IB4 event occurred and
transferred the Since 0 count value to the Since 1 count value.
See “Operations Since” Counter in Chapter 4 for a more detailed
description of this feature.