Parameters B-35
1503-UM054C-EN-P June 2013
DeviceNet Voltage [24V DeviceNet Voltage]
Parameter Number: 64,52,40,28,16.
Access rule: Get
Data Type: FLOAT
Object Mapping: 0x3-1-100
Group: Control
Units : Volts
Minimum Value: 0V
Maximum Value: 50.000V
Default Value: 0V
This parameter allows the user to view the DeviceNet DC voltage
level.
15V Supply Voltage from the IB [15V IB Voltage]
Parameter Number: 65,53,41,29,17.
Access rule: Get
Data Type: FLOAT
Object Mapping: 0x3-1-101
Group: Control
Units : Volts
Minimum Value: 0V
Maximum Value: 30.000V
Default Value: 0V
This parameter allows the user to view the DC supply voltage level
from the IB board.
DeviceLogix Program Selection [Preload DeviceLogix Program]
Parameter Number: 66,54,42,30,_.
Access rule: Get/Set
Data Type: USINT
Object Mapping: 0xB4-1-114
Group: Control
Units : -
Minimum Value: 0 = User customized DeviceLogix Prog.
Maximum Value: 5 = PFCC DeviceLogix Program
Default Value: 0
This parameter allows the user to view, as well as to select, the
DeviceLogix program that will be executed. There are six different
programs that can be selected. This is shown in the following
RSNetworx screen in Figure B.2.
For each of the Programs listed, a status of0’ indicates that the
Program is disabled and a status of1’ indicates that the Program is
enabled.